3-8 Installing the Controller Link Interface Unit
3-57
6. Carefully insert the signal and shield lines into the respective holes of the connector
(identified with the markings). Ensure that the connector is oriented correctly. The follow-
ing example is for connection to a Board in the middle of the network.
Cable connector
Shield lines
BD H
BD L
Precautions
for Safe Use
•
Loosen the screws in the connector enough to allow the terminal to pass be-
fore inserting the signal line. If the screw is not loosened, the signal line will
go completely into the connector and you will not be able to secure the line.
•
Attach crimp terminals to the wires. Never connect bare power supply wires
directly to the connector.
Reference
•
Marks are provided on the connector for the signal lines. Connect the signal lines ac-
cording to the marks.
•
Marks indicate signals as listed above.
•
The lines can be connected to either the right or left half of the connector at the node
on either end of the network.
•
If grounding by node, the connection method for the shield is different.
Refer to
Wiring Communications Cable
and
Connecting the Shield Line to the Connec-
tor
under
3-8-4
Wiring,
for details on connecting the shield to the connector.
7. Firmly secure each signal line with the signal line screws in the connector. An ordinary
flat-blade screwdriver with a tip that tapers at the end is not suitable because it cannot
be inserted far enough. Use a small flat-blade screwdriver with a uniform width. The ap-
plicable tightening torque is 0.2 N
⋅
m.
Marking
Signal name
Line color
BD H (communications data high) Black
BD L (communication data low)
White
S SHLD
(shield)
−
Summary of Contents for NS15-V2 Series
Page 1: ...Cat No V083 E1 14 Programmable Terminals NS Series SETUP MANUAL...
Page 2: ......
Page 34: ...1 4 Procedure for Running NS series PTs 1 12...
Page 54: ...2 2 Part Names and Functions 2 20...
Page 144: ...4 4 Recommended Connector Cables 4 28...
Page 174: ...5 3 Connecting to Host via EtherNet IP 5 30...
Page 246: ...6 11 Verifying Tags 6 72...
Page 280: ...Appendix 2 Dimensions A 20 NS5 V1 V2 Cable Connection Dimensions...
Page 333: ......
Page 334: ......