4-1 1:1 Host Connection
4-5
•
Setting the Front Panel DIP Switch
Using RS-232C
When using C200HX/HG/HE(-Z), CQM1, or CQM1H PLCs, set the DIP switch on the front
panel to enable the PLC Setup Area (Data Memory) settings, as follows:
C200HX/HG/HE(-Z)
CQM1
RS-232C Communications Conditions Setting
Set pin 5 of the DIP switch to OFF to enable the
PLC Setup Area settings.
CQM1H
•
Setting the CPM2A Front Panel DIP Switch
When using a CPM2A, set the DIP switch on the front panel to enable the PLC Setup Area
(Data Memory) settings, as follows:
Set the communications
conditions setting switch to
OFF (lower position).
•
Setting the CPM2C Front Panel DIP Switches
When using a CPM2C, set the switches on the front panel to enable the PLC Setup Area
(Data Memory) settings, as follows:
Set the switches according to whether the peripheral port or
the built-in RS-232C port is used, as follows:
•
Connecting the PT to the built-in RS-232C port
(The peripheral port is used to connect devices that require
non-standard communications settings.)
SW1: OFF
SW2: ON
SW1: OFF
SW2: OFF
•
Connecting the PT to the built-in RS-232C port
(The peripheral port is used to connect the Programming
Console.)
Summary of Contents for NS15-V2 Series
Page 1: ...Cat No V083 E1 14 Programmable Terminals NS Series SETUP MANUAL...
Page 2: ......
Page 34: ...1 4 Procedure for Running NS series PTs 1 12...
Page 54: ...2 2 Part Names and Functions 2 20...
Page 144: ...4 4 Recommended Connector Cables 4 28...
Page 174: ...5 3 Connecting to Host via EtherNet IP 5 30...
Page 246: ...6 11 Verifying Tags 6 72...
Page 280: ...Appendix 2 Dimensions A 20 NS5 V1 V2 Cable Connection Dimensions...
Page 333: ......
Page 334: ......