6-8 Special Screens
6-56
FINS Communications Test
1. Set each of the setting items, as follows:
•
Setting and Display Items in Communication Test Screen
Item
Details
Send to
Sets the address of the transmission destination in the format
(network ad-
dress).(node address).(unit number)
.
Sets the following addresses when performing a communications test for a node
connected to serial port A or B.
•
Serial port A:
111.1.0
•
Serial port B:
112.1.0
Send message Sets the FINS command being to be sent.
Number of
sends
Displays the number of times messages are transmitted. The number of times is
fixed to 1.
Receive Time-
out
Sets the time before the message timeout occurs. Displays an error message
when the timeout time is exceeded after transmission.
The setting time is applicable for Ethernet only. For serial communications, the
timeout monitor time set from the Comm
Tab is used.
2. Press
the
Start
Button to start transmission.
The sending indicator will remain lit until the transmission is completed.
After transmission, the Receiving indicator will remain lit until reception is completed.
3. If communications are normal, a response will be received from the transmission destination and
the following items will be displayed. Refer to the
FINS Command Reference Manual
(Cat. No.
W227) for details on FINS commands and information displayed in comments.
•
Display Items in Communication Test Screen
Item
Details
SID (See note 1.)
The SID used for transmission is displayed as a hexadecimal.
The SID is incremented between 0 and 0xFF and returns to 0 after 0xFF is
exceeded.
Received header
Displays the FINS header that is received. (See note 2.)
Received message Displays the received message.
ms
Displays the time lapsed in ms from sending the FINS command until re-
ceiving the FINS response.
Comment
Displays the status, such as "normal completion," according to the comple-
tion code after reception.
Note 1. SID is the source process ID.
2. The FINS header is the header that precedes the FINS command. Refer to the
FINS Com-
mand Reference Manual
(Cat. No. W227)
for details on FINS commands.
Summary of Contents for NS15-V2 Series
Page 1: ...Cat No V083 E1 14 Programmable Terminals NS Series SETUP MANUAL...
Page 2: ......
Page 34: ...1 4 Procedure for Running NS series PTs 1 12...
Page 54: ...2 2 Part Names and Functions 2 20...
Page 144: ...4 4 Recommended Connector Cables 4 28...
Page 174: ...5 3 Connecting to Host via EtherNet IP 5 30...
Page 246: ...6 11 Verifying Tags 6 72...
Page 280: ...Appendix 2 Dimensions A 20 NS5 V1 V2 Cable Connection Dimensions...
Page 333: ......
Page 334: ......