Appendix 3 Using NS-AL002 Converters
A-25
Crimp Terminals
Use M3 crimp terminals.
Forked type
Round type
6.2 mm max.
6.2 mm max.
Applicable Crimp Terminal Examples
Forked type
Manufacturer Model
Recommended cable size
J.S.T. Mfg. Co., Ltd.
V1.25-N3A
AWG22 to 16 (0.25 to 1.65 mm
2
)
Molex
VSY1.25-3.5L
AWG22 to 16 (0.3 to 1.65 mm
2
)
Round type
Manufacturer Model
Recommended cable size
J.S.T. Mfg. Co., Ltd.
V1.25-MS3
AWG22 to 16 (0.25 to 1.65 mm
2
)
Molex
RAV1.25-3
AWG22 to 16 (0.3 to 1.65 mm
2
)
Recommended Cable
Manufacturer Model
Tachii Electric Wire Co., Ltd.
TKV VBS3P-03
HIRAKAWA HEWTECH CORP.
CO-HC-ESV-3P
×
7/0.2
A-3-6 Handling the Shield on RS-422A/485 Cables
Perform the following procedures to connect, process the shield, and connect to ground
for communications systems using the NS-AL002. Incorrect connection may result in
communications errors with the host.
Connecting the NS-AL002 D-Sub Connector
Always securely tighten the screws on both sides of the D-Sub connector. Otherwise, the
functional ground terminal (FG: ) of the PT will not be properly connected to the func-
tional ground of the NS-AL002.
Connecting the Ground Wire
The PT has a functional ground terminal (FG: ).
1. Ground
according
to
Figure (a)
for normal grounding.
•
Connect the ground terminal (GR) of the devices to the functional ground (FG: ).
Make sure that each signal line is grounded at only one point and ground to 100
Ω
max.
•
Short the LG terminal of the PLC to the ground terminal (GR).
•
Use a wire gauge of at least 2 mm
2
for the ground wire.
•
Refer to the manual for individual Communications Units for details on proper wiring
procedures.
2. Do not ground the functional ground (FG: ) of the PT if it is mounted to the same
panel as devices that generate noise, such as motors or inverters, as shown in
Figure
(b)
.
Summary of Contents for NS15-V2 Series
Page 1: ...Cat No V083 E1 14 Programmable Terminals NS Series SETUP MANUAL...
Page 2: ......
Page 34: ...1 4 Procedure for Running NS series PTs 1 12...
Page 54: ...2 2 Part Names and Functions 2 20...
Page 144: ...4 4 Recommended Connector Cables 4 28...
Page 174: ...5 3 Connecting to Host via EtherNet IP 5 30...
Page 246: ...6 11 Verifying Tags 6 72...
Page 280: ...Appendix 2 Dimensions A 20 NS5 V1 V2 Cable Connection Dimensions...
Page 333: ......
Page 334: ......