4-2 1:N Host Connection
4-10
Item Description
Baud
Select the Custom Option and set the baud rate to 38,400 bps (Standard 1:N
NT Link Mode). The format does not need to be changed.
Mode
Set the mode to the 1:N NT Link Mode.
NT/PLC
Link Max.
If only one PT is connected to the port and it has a unit number of 0, set this
parameter to 1. Otherwise, set the highest unit number of all the PTs that are
connected.
Using a Programming Console
If the PT is connected to the Host Link port (RS-232C port), connect the Programming Con-
sole to the CPU Unit and set the following values at the specified addresses of the PLC
Setup.
PLC
Setup
address
Setting to write
Description
160
8200 hex
Specifies using the Host Link port in 1:N NT Link Mode.
161
0000 to 0009 hex
Specifies the standard communications speed (38,400
bps). It does not matter what value between 0000 and
0009 is set.
166
000
@
hex
If only one PT is connected to the port and it has a unit
number of 0, replace the box at the left with 1. Otherwise,
replace the box with the highest unit number of all the PTs
that are connected.
Reference
If the PT is connected to the peripheral port make the above settings in words 144, 145,
and 150 of the PLC Setup instead of 160, 161, 166.
Summary of Contents for NS15-V2 Series
Page 1: ...Cat No V083 E1 14 Programmable Terminals NS Series SETUP MANUAL...
Page 2: ......
Page 34: ...1 4 Procedure for Running NS series PTs 1 12...
Page 54: ...2 2 Part Names and Functions 2 20...
Page 144: ...4 4 Recommended Connector Cables 4 28...
Page 174: ...5 3 Connecting to Host via EtherNet IP 5 30...
Page 246: ...6 11 Verifying Tags 6 72...
Page 280: ...Appendix 2 Dimensions A 20 NS5 V1 V2 Cable Connection Dimensions...
Page 333: ......
Page 334: ......