4-2 1:N Host Connection
4-15
Setting the Front Panel Switches
•
Using RS-422A
Port 1
RS-232C
Port 2
RS-422A
Terminating resistance switch (TERM)
Set to ON:
Terminating resistance used
(right position)
Two-wire/four-wire switch (WIRE)
For RS-422A:
Set to 4 for four-wire (right position).
Connecting to CS-series Serial Communications Units
CS-series Rack-mounted Type:
CS1W-SCU21 (Both ports 1 and 2 are RS-232C ports.)
CS1W-SCU31 (Both ports 1 and 2 are RS-422A ports.)
CPU Unit DM Area Settings
•
Using RS-232C
Write the settings directly from the Programming Device or Support Software (Programming
Console or CX-Programmer) to the DM Area (Parameter Area) in the CPU Unit. After writing
the settings, enable the settings by turning ON the power again, restarting the Unit, restart-
ing the communications port, or executing the CHANGE SERIAL PORT SETUP (STUP) in-
struction.
The following table shows the allocated DM Area words and settings.
m = 30000 + 100
×
unit number
Allocated DM Area words
Port 1
Port 2
Write
value Settings
DM m
DM m + 10
8200
1:N NT Link Mode
DM m + 1
DM m + 11
0000 to 0009 (See note 1.) Baud rate (normal)
DM m + 6
DM m + 16
000
@
@
: Largest unit number (1 to 7) of the
connected PTs. (See note 2.)
Note 1. Set the baud rate to a numeric value between 0000 to 0009 Hex. (The setting is the same for
any value between 0000 and 0009 Hex.)
2. When using a 1:N connection, set the value for
@
to 1 or higher.
Reference
When setting a 1:N NT Link in the CX-Programmer, set the baud rate to 38,400 bps.
Summary of Contents for NS15-V2 Series
Page 1: ...Cat No V083 E1 14 Programmable Terminals NS Series SETUP MANUAL...
Page 2: ......
Page 34: ...1 4 Procedure for Running NS series PTs 1 12...
Page 54: ...2 2 Part Names and Functions 2 20...
Page 144: ...4 4 Recommended Connector Cables 4 28...
Page 174: ...5 3 Connecting to Host via EtherNet IP 5 30...
Page 246: ...6 11 Verifying Tags 6 72...
Page 280: ...Appendix 2 Dimensions A 20 NS5 V1 V2 Cable Connection Dimensions...
Page 333: ......
Page 334: ......