![background image](http://html.mh-extra.com/html/omron/ns-rev-12/ns-rev-12_setup-manual_744517098.webp)
3-8 Installing the Controller Link Interface Unit
3-44
Indicators
Indicator Name Color
status
Meaning
RUN Operating Green
Lit Normal
operation.
Not lit
A Board operating error (watchdog timer error) oc-
curred.
ERC Communica-
tions error
Red
Lit
One of the following errors occurred.
•
Communications error
•
Same node address used twice (i.e., address
duplication error)
•
Hardware error
Not lit
Normal operation
ERH
EEPROM error Red
Lit
One of the following errors occurred.
•
EEPROM error
•
EEPROM data link table error
•
EEPROM routing table error
•
EEPROM network parameter error
Not lit
No EEPROM error.
INS Network
par-
ticipation
Yellow
Lit
The Board is participating in the network.
Not lit
The Board is not participating in the network.
SD Send
Yellow
Lit Sending
data.
Not lit
Not sending data.
RD Receive Yellow
Lit Receiving
data.
Not lit
Not receiving data.
LNK Data
link
Yellow
Lit
Participating in data link.
Flash-
ing
Error in data link table setting.
Not lit
Not participating in data link or data link inactive.
Summary of Contents for NS - REV 12
Page 2: ......
Page 22: ...20 ...
Page 34: ...1 4 Procedure for Running NS series PTs 1 12 ...
Page 54: ...2 2 Part Names and Functions 2 20 ...
Page 116: ...3 11 RS 232C RS 422A Selector DIP Switch 3 62 ...
Page 144: ...4 4 Recommended Connector Cables 4 28 ...
Page 174: ...5 3 Connecting to Host via EtherNet IP 5 30 ...
Page 246: ...6 11 Verifying Tags 6 72 ...
Page 279: ...Appendix 2 Dimensions A 19 NS5 V1 V2 Cable Connection Dimensions ...
Page 332: ......
Page 333: ......