3-8 Installing the Controller Link Interface Unit
3-45
Switch Settings
The following settings are made at the factory. Do not change these settings.
Item Switch Setting
Memory address
Memory allocation switch
SW1: ON
SW2: ON
SW3: OFF
SW4: ON
Interrupt level
Interrupt shorting pin
Set to IRQ10.
Setting Terminating Resistance
Turn the built-in terminating resistance ON or OFF using the terminating resistance switch
(slide switch). Terminating resistance is required at the both ends of a wired network to ab-
sorb unnecessary signals and reduce the noise. The Controller Link Support Board has built-
in terminating resistance, which can be connected simply by setting the slide switch to ON.
Set the switch to ON to connect the terminating resistance at both end nodes in wired net-
works and set the switch to OFF at all other nodes.
ON
Setting Terminating
resistance
OFF (factory setting) Not connected
ON Connected
Precautions
for Safe Use
This switch can be set after the Controller Link Interface Unit is installed on the
PT.
Turn OFF the power of the PT before changing the setting.
Reference
This switch is set to OFF by default (terminating resistance disconnected).
Summary of Contents for NS - REV 12
Page 2: ......
Page 22: ...20 ...
Page 34: ...1 4 Procedure for Running NS series PTs 1 12 ...
Page 54: ...2 2 Part Names and Functions 2 20 ...
Page 116: ...3 11 RS 232C RS 422A Selector DIP Switch 3 62 ...
Page 144: ...4 4 Recommended Connector Cables 4 28 ...
Page 174: ...5 3 Connecting to Host via EtherNet IP 5 30 ...
Page 246: ...6 11 Verifying Tags 6 72 ...
Page 279: ...Appendix 2 Dimensions A 19 NS5 V1 V2 Cable Connection Dimensions ...
Page 332: ......
Page 333: ......