7-3 Troubleshooting and Maintenance
7-9
Message Cause
Possible
countermeasure
ERROR No. 11: Fail in load-
ing files: Please reinstall the
system program.
File reading failed.
ERROR No. 11: Device
check program error: Please
reinstall the system pro-
gram.
Hardware check program is
corrupted.
ERROR No. 11: SRAM
check program error: Please
reinstall the system pro-
gram.
Log SRAM check program
is corrupted.
ERROR No. 11: IP Address
Setting Error: Please rein-
stall the system program.
IP address setting program
is corrupted.
Execute automatic download of the
system program. If the same problem
occurs after downloading, insert the
Memory Card containing the recov-
ery program in the PT and reset the
PT or turn the power supply OFF and
ON again. (Refer to
3-6 Using Mem-
ory Cards
in the
Setup Manual
.) If the
same problem occurs after reinstall-
ing the system program, contact your
nearest OMRON representative.
ERROR No. 11: Device
check program error: Touch
the screen to continue.
At startup with DIP switch 6
set to ON, the hardware
check program is corrupted.
The Memory Card transfer program
started up after this can be used. If
operation is not restored after con-
tinuing with the Memory Card trans-
fer program, insert the Memory Card
containing the recovery program in
the PT and reset the PT or turn the
power supply OFF and ON again.
(Refer to
3-6 Using Memory Cards
in
the
Setup Manual
.) If the same prob-
lem occurs after reinstalling the sys-
tem program, contact your nearest
OMRON representative.
ERROR No. 12: Fail in load-
ing fonts: Please reinstall
the system program.
Reading of font files when
operation performed with
DIP switch 6 set to ON
failed.
ERROR No. 12: Installed
system program is not ap-
plicable for this hardware:
Please reinstall the system
program.
The installed system pro-
gram does not match the
hardware.
Download the system program by
automatic download that does not
use DIP switch 6. If operation is not
restored after downloading, insert the
Memory Card containing the recov-
ery system program in BANK 1 in the
PT. (Refer to
3-6 Using Memory
Cards
in the
Setup Manual
.) If the
same problem occurs after reinstall-
ing the system program, contact your
nearest OMRON representative.
WARNING No. 20: Date and
Time are not set: Touch the
screen to continue.
Date set outside the PT’s
allowable range of 2000 to
2049.
Touch the touch panel to continue
booting. Then set the correct date in
the System Menu.
WARNING No. 21: SRAM
previously broken…
Initialization Complete:
Touch the screen to con-
tinue.
SRAM contents could not
be held because the battery
was not connected or there
was insufficient capacity.
For this reason, SRAM was
initialized.
Touch the touch panel to continue
booting. Replace the battery the next
time power is turned OFF.
Summary of Contents for NS - REV 12
Page 2: ......
Page 22: ...20 ...
Page 34: ...1 4 Procedure for Running NS series PTs 1 12 ...
Page 54: ...2 2 Part Names and Functions 2 20 ...
Page 116: ...3 11 RS 232C RS 422A Selector DIP Switch 3 62 ...
Page 144: ...4 4 Recommended Connector Cables 4 28 ...
Page 174: ...5 3 Connecting to Host via EtherNet IP 5 30 ...
Page 246: ...6 11 Verifying Tags 6 72 ...
Page 279: ...Appendix 2 Dimensions A 19 NS5 V1 V2 Cable Connection Dimensions ...
Page 332: ......
Page 333: ......