![background image](http://html.mh-extra.com/html/omron/ns-rev-12/ns-rev-12_setup-manual_744517263.webp)
Appendix 1 Specifications
A-3
Appendix 1
Specifications
A-1-1 General
Specifications
Specifications
Item
NS15-TX01
@
-V2
NS12-TS0
@
-V1
NS12-TS0
@
-V2
NS10-TV0
@
-V1
NS10-TV0
@
-V2
NS8-TV
@@
-V1
NS8-TV
0@
-V2
NS5-SQ0
@
-V1
NS5-
S
Q
@@
-V2
NS5-
T
Q
@@
-V2
NS5-
M
Q
@@
-V2
Rated power
supply voltage
24 VDC
Allowable volt-
age range
20.4 to 27.6 VDC (24 VDC
±
15%)
Allowable input
power interrup-
tion time
No restriction.
Power consump-
tion
45 W max.
25 W max
15 W max.
Ambient operat-
ing
temperature
0 to 50
°
C (See notes 1, 2, and 3.)
Storage
temperature
−
20 to 60
°
C (See note 2.)
Ambient operat-
ing
humidity
35% to 85% (0 to 40
°
C) with no condensation
35% to 60% (40 to 50
°
C) with no condensation
Operating envi-
ronment
No corrosive gases.
Noise immunity
Conforms to IEC61000-4-4, 2 KV (power lines)
Vibration resis-
tance
(during opera-
tion)
5 to 8.4 Hz with
3.5 mm single
amplitude and 8.4
to 150 Hz with 9.8
m/s
2
acceleration
10 times in each of
X, Y, and Z direc-
tions
10 to 57 Hz with 0.075 mm amplitude and 57 to 150 Hz with 9.8 m/s
2
accelera-
tion for 30 min in each of X, Y, and Z directions
Shock resistance
(during opera-
tion)
147 m/s
2
3 times in each of X, Y, and Z directions.
Dimensions 405
×
304
×
75.8 mm
(W
×
H
×
D)
315
×
241
×
48.5 mm (W
×
H
×
D)
232
×
177
×
48.5 mm
(W
×
H
×
D)
195
×
142
×
54 mm
(W
×
H
×
D)
Panel cutout
dimensions
Width 383.5
+1
0
×
Height
282.5
+1
0
mm
Panel thickness:
1.6 to 4.8 mm
Width 302
+1
0
×
Height
228
+1
0
mm
Panel thickness:
1.6 to 4.8 mm
Width 302
+1
0
×
Height
228
+1
0
mm
Panel thickness:
1.6 to 4.8 mm
Width
220.5
+0.5
0
×
Height 165.5
+0.5
0
mm
Panel thickness:
1.6 to 4.8 mm
Width 184
+0.5
0
×
Height 131
+0.5
0
mm
Panel thickness:
1.6 to 4.8 mm
Weight
4.2 kg max.
2.5 kg max.
2.0 kg max.
1.0 kg max.
Enclosure rating
Front panel: IP65 oil-proof type (equivalent to NEMA4) (See note 4.)
Battery life
5 years (at 25
°
C)
The SRAM and RTC will be backed up for 5 days after the battery runs low (indicator lights orange).
The SRAM and RTC will be backed up by a super capacitor for 5 minutes after removing the old
battery (i.e., after turning ON power after 5 minutes).
International
standards
EC Directives
UL 1604 Class 1 Division 2, EC Directives
Note 1. The operating temperature is subject to the following restrictions, depending on the
mounting angle and whether an Expansion Unit is installed or not.
Summary of Contents for NS - REV 12
Page 2: ......
Page 22: ...20 ...
Page 34: ...1 4 Procedure for Running NS series PTs 1 12 ...
Page 54: ...2 2 Part Names and Functions 2 20 ...
Page 116: ...3 11 RS 232C RS 422A Selector DIP Switch 3 62 ...
Page 144: ...4 4 Recommended Connector Cables 4 28 ...
Page 174: ...5 3 Connecting to Host via EtherNet IP 5 30 ...
Page 246: ...6 11 Verifying Tags 6 72 ...
Page 279: ...Appendix 2 Dimensions A 19 NS5 V1 V2 Cable Connection Dimensions ...
Page 332: ......
Page 333: ......