3-6 Using Memory Cards
3-23
3-6-2 Replacing
the
System Program
The system program in the PT can be replaced or upgraded to a higher version. There are
two methods that can be used to replace the system program.
•
Using a recovery/upgrade program
•
Transferring system program data
Using a Recovery/Upgrade Program
For details on the recovery/update program, select
Start - Program - OMRON - CX-One -
CX-Designer NS Most Recent NS-series PT Update/Recovery Procedure
.
Transferring System Program Data
When System Program Ver. 8.1 is selected and loaded with the CX-Designer, it is stored un-
der the CX-Designer’s install folder (default location is C:\Program Files\Omron\CX-One\CX-
Designer) in folders that are created for each type and version, as follows:
\SystemBackup\NS15\V8_1\bank1:
Ver. 8.1 for NS15
\NS12_V1_V2\V8_1\bank1:
Ver. 8.1 for NS12
\NS10_V1_V2\V8_1\bank1:
Ver. 8.1 for NS10
\NS8_V1_V2\V8_1\bank1:
Ver. 8.1 for NS8
\NS5_V1_V2\V8_1\bank1:
Ver. 8.1 for NS5
To replace a system program, use Windows Explorer or another method to copy each of the
folders for the required system program under \bank1 to the route directory of the Memory
Card.
For details on methods for transferring data from the Memory Card to the PT, refer to
3-6-3
Transferring Data with Memory Cards
.
The system backup folder can be created only if CX-Designer is installed from the stand-
alone CD-ROM. If the CX-Designer is installed from CX-One, reinstall the system program by
following the procedure for using a recovery/update program described above.
Restrictions on System Program Replacement
Starting the PT may become impossible if the system program replacement procedure is not
performed correctly. Observe the following precautions.
•
When upgrading the system program (or replacing it with a previous version), use the re-
covery/update program at least the first time.
•
System program version 6.2 or higher must be used to replace the system program in the
NS5-SQ0
@
-V2, NS5-TQ0
@
-V2, or NS5-MQ0
@
-V2. If an earlier system program version is
used, screens may not be displayed properly. If an earlier version is installed by mistake,
use the recovery/update program and upgrade to system program version 6.2 or higher.
•
System program version 8.0 or higher must be used to replace the system program in the
NS5-SQ1
@
-V2, NS5-TQ1
@
-V2, or NS5-MQ1
@
-V2. Earlier versions cannot be used.
•
System program version 8.1 or higher must be used to replace the system program in the
NS15-TX01
@
-V2. You cannot replace the system program with a system program of a
lower version.
Summary of Contents for NS - REV 12
Page 2: ......
Page 22: ...20 ...
Page 34: ...1 4 Procedure for Running NS series PTs 1 12 ...
Page 54: ...2 2 Part Names and Functions 2 20 ...
Page 116: ...3 11 RS 232C RS 422A Selector DIP Switch 3 62 ...
Page 144: ...4 4 Recommended Connector Cables 4 28 ...
Page 174: ...5 3 Connecting to Host via EtherNet IP 5 30 ...
Page 246: ...6 11 Verifying Tags 6 72 ...
Page 279: ...Appendix 2 Dimensions A 19 NS5 V1 V2 Cable Connection Dimensions ...
Page 332: ......
Page 333: ......