3-8 Installing the Controller Link Interface Unit
3-56
6. Carefully insert the signal and shield lines into the respective holes of the connector
(identified with the markings). Ensure that the connector is oriented correctly. The follow-
ing example is for connection to a Board in the middle of the network.
Cable connector
Shield lines
BD H
BD L
Precautions
for Safe Use
•
Loosen the screws in the connector enough to allow the terminal to pass
before inserting the signal line. If the screw is not loosened, the signal line
will go completely into the connector and you will not be able to secure the
line.
•
Attach crimp terminals to the wires. Never connect bare power supply wires
directly to the connector.
Reference
•
Marks are provided on the connector for the signal lines. Connect the signal lines ac-
cording to the marks.
•
Marks indicate signals as listed above.
•
The lines can be connected to either the right or left half of the connector at the node
on either end of the network.
•
If grounding by node, the connection method for the shield is different.
Refer to
Wiring Communications Cable
and
Connecting the Shield Line to the Con-
nector
under
3-8-4
Wiring,
for details on connecting the shield to the connector.
7. Firmly secure each signal line with the signal line screws in the connector. An ordinary
flat-blade screwdriver with a tip that tapers at the end is not suitable because it cannot be
inserted far enough. Use a small flat-blade screwdriver with a uniform width. The applica-
ble tightening torque is 0.2 N
⋅
m.
Marking
Signal name
Line color
BD H (communications data high) Black
BD L (communication data low)
White
S SHLD
(shield)
−
Summary of Contents for NS - REV 12
Page 2: ......
Page 22: ...20 ...
Page 34: ...1 4 Procedure for Running NS series PTs 1 12 ...
Page 54: ...2 2 Part Names and Functions 2 20 ...
Page 116: ...3 11 RS 232C RS 422A Selector DIP Switch 3 62 ...
Page 144: ...4 4 Recommended Connector Cables 4 28 ...
Page 174: ...5 3 Connecting to Host via EtherNet IP 5 30 ...
Page 246: ...6 11 Verifying Tags 6 72 ...
Page 279: ...Appendix 2 Dimensions A 19 NS5 V1 V2 Cable Connection Dimensions ...
Page 332: ......
Page 333: ......