74
Frame Configuration
Section 6-2
End Codes (CompoWay/F Communications)
End code
Name
Description
“0F”
FINS command error The specified FINS command could not be executed.
“10”
Parity error
The OR of 1 bits in received data does not match the set-
ting for the communications parity.
“11”
Framing error
Stop bit is “0”.
“12”
Overrun error
The next data was received when the reception data buffer
was full.
“13”
BCC error
The calculated BCC value is different from the received
BCC value.
“14”
Format error
The FINS-mini command text contains characters other
than 0 to 9 and A to F. For details on the echoback test,
refer to 6-10 Echo-back Test.
SID and the FINS-mini command text are not included.
“16”
Sub-address error
The sub-address is not included.
“18”
Frame length error
The received frame exceeds the required number of bytes.
“00”
Normal completion
Command processing was completed normally.
Summary of Contents for G3PW
Page 1: ...Cat No Z280 E1 01 User s Manual G3PW Power Controllers...
Page 2: ...G3PW Power Controllers User s Manual Produced November 2008...
Page 3: ...iv...
Page 15: ...xvi...
Page 49: ...34 Wiring for Specific Applications Section 3 4...
Page 61: ...46 Setting Parameters in the Initial Setting Level Section 4 6...
Page 77: ...62 Heater Burnout Detection Section 5 9...
Page 113: ...98 Parameter Settings in the Adjustment Level Appendix B...
Page 117: ...102 Index...
Page 119: ......