96
Parameters Set in Initial Setting Level
Appendix A
*
1
Constant-current Models only.
p15
Total Run Time
Exceeded Alarm
Operation
Sets the alarm level to use when the total run time exceeds the set value.
0
: Disable (Default)
1
: Alarm level 1 (fatal error)
2
: Alarm level 2 (nonfatal error)
p16
Total Run Time Alarm
Set Value
*
1
An alarm is output when the total run time exceeds the set value.
0.0 to 99.9 kh
0.0
: This function stops when the parameter is set to 0.0. (Default)
p17
External Input Range
Alarm Operation
Sets the alarm level when an external variable resistor disconnection occurs or
when the 4 to 20-mA or 1 to 5-V input range is exceeded.
0
: Disable (Default)
1
: Alarm level 1 (fatal error)
2
: Alarm level 2 (nonfatal error)
p18
External Duty Input
Alarm Operation
Sets the alarm level when an external duty variable resistor disconnection occurs
or when the 4 to 20-mA or 1 to 5-V input range is exceeded.
0
: Disable (Default)
1
: Alarm level 1 (fatal error)
2
: Alarm level 2 (nonfatal error)
p19
Communications Unit
Number
*
1
Sets the Communications unit number for CompoWay/F.
0 to 99 (Default: 1)
p20
Communications
Baud Rate
*
1
Sets the baud rate for CompoWay/F.
9.6
: 9.6 k bit/s
19.2
: 19.2 k bit/s
38.4
: 38.4 k bit/s
57.6
: 57.6 k bit/s (Default)
p21
Communications
Data Length
*
1
Sets the data length for communications.
7
: 7 bits (Default)
8
: 8 bits
p22
Communications
Stop Bits
*
1
Sets the number of stop bits for communications.
1
: 1 bit
2
: 2 bits (Default)
p23
Communications Par-
ity
*
1
Sets the parity for communications.
non
: None
evn
: Even (Default)
odd
: Odd
p24
Send Wait Time
*
1
Sets the send wait time.
0 to 99 ms (Default: 1)
p25
Communications
Main Setting Num-
ber
*
1
Sets the MV input channel.
• Connection to an OMRON EJ1 Modular Temperature Controller
0
: Automatic assignment (recommended) (Default)
1
: CH1 control output (heating)
5
: CH1 control output (cooling)
2
: CH2 control output (heating)
6
: CH2 control output (cooling)
3
: CH3 control output (heating)
7
: CH3 control output (cooling)
4
: CH4 control output (heating)
8
: CH4 control output (cooling)
• Connection to an OMRON PLC
1
: CH1
p26
Communications Tim-
eout Time
*
1
0 to 999 s (Default: 10)
0
: Communications timeout function disabled
p27
Reset Total Run Time Used to reset the total run time.
abt
: Do not reset. (Default)
ini
: Initialize.
p28
Initialize Set Values
Used to initialize parameter settings.
abt
: Do not initialize. (Default)
ini
: Initialize.
Display
Name
Setting
Summary of Contents for G3PW
Page 1: ...Cat No Z280 E1 01 User s Manual G3PW Power Controllers...
Page 2: ...G3PW Power Controllers User s Manual Produced November 2008...
Page 3: ...iv...
Page 15: ...xvi...
Page 49: ...34 Wiring for Specific Applications Section 3 4...
Page 61: ...46 Setting Parameters in the Initial Setting Level Section 4 6...
Page 77: ...62 Heater Burnout Detection Section 5 9...
Page 113: ...98 Parameter Settings in the Adjustment Level Appendix B...
Page 117: ...102 Index...
Page 119: ......