56
Load Current Limit (Constant-current Models Only)
Section 5-7
5-7
Load Current Limit (Constant-current Models Only)
The load current limit function is used to measure the load current with the
built-in CT and to limit the load current by adjusting the output phase angle so
that the load current does not exceed the value set in the Load Current Upper
Limit parameter [P10].
• The load current upper limit is set in the Load Current Upper Limit param-
eter [P10] in the initial setting level.
• This function can be used with Constant-current Models only.
• When this function is being used, the output value that is actually output
will be smaller than the output value that is calculated based on the input
value.
• The following example shows the load current limit function used when
the maximum load current is 20 A.
!Caution
The load current limit function cannot be used to suppress the inrush current
for loads with a large inrush current. For loads with a large inrush current, use
the load current limit function together with the soft-start up function to sup-
press the inrush current. The response time that is required before the load
current can be suppressed is 500 ms max.
Setting range
0.0 to 66.0 (A)
20
0
100
16
80
Load current (A)
Load current upper limit
= 16 A
Output value (%)
Summary of Contents for G3PW
Page 1: ...Cat No Z280 E1 01 User s Manual G3PW Power Controllers...
Page 2: ...G3PW Power Controllers User s Manual Produced November 2008...
Page 3: ...iv...
Page 15: ...xvi...
Page 49: ...34 Wiring for Specific Applications Section 3 4...
Page 61: ...46 Setting Parameters in the Initial Setting Level Section 4 6...
Page 77: ...62 Heater Burnout Detection Section 5 9...
Page 113: ...98 Parameter Settings in the Adjustment Level Appendix B...
Page 117: ...102 Index...
Page 119: ......