![Omron G3PW User Manual Download Page 65](http://html1.mh-extra.com/html/omron/g3pw/g3pw_user-manual_742699065.webp)
50
Inputting the Main Setting with an External Variable Resistor
Section 5-2
5-2
Inputting the Main Setting with an External Variable
Resistor
The setting procedure shown here is for when the main setting is input by
using an external variable resistor.
1,2,3...
1.
In the initial setting level, set the Event Input Assignment parameter [P11]
to 0 (no assignment) or 1 (control method selection).
2.
In the initial setting level, set the Main Setting Automatic/Manual Default
parameter [P08] to 1 (manual). If automatic or manual operation is select-
ed using the event input, the setting for the event input will be given priority.
3.
Set the Main Setting Manual Input Selection [P06] to 0 (external variable
resistor input).
4.
Use the ENT/RST Key to reset the Power Controller, and set the Main Set-
ting Automatic/Manual Default parameter [P08] to Enable. If automatic or
manual operation is selected using the event input, the Power Controller
reset is not required.