88
Checking Possible Errors
Section 7-1
7-1
Checking Possible Errors
Troubleshooting
Check Flow When There Is No Output
Check the output value (OUT) on the 7-
segment display.
Output occurs.
(value not 0.0)
Check for problems in the load
wiring.
No output occurs (value is 0.0).
Check for problems in the input signal
wiring.
No problem
Check whether the duty setting (DUTY)
is 0.0.
Increase the duty setting.
The setting
is 0.0.
The setting is
not 0.0.
Check whether the output upper limit
(OLU) is 0.0.
The setting is
not 0.0.
The setting
is 0.0.
Increase the output upper limit.
Check whether the Input Signal Type
[P04] setting is correct.
The setting is correct.
Check whether the Main Setting
Automatic/Manual Default [P08] setting is
correct.
Automatic input
The setting is correct.
Check whether the Main Setting
Automatic Input Selection [P05] setting is
correct.
Manual input
Check whether the Main Setting Manual
Input Selection [P06] setting is correct.
The communications
input is correctly set.
Check whether the Communications Main
Setting Number [P25] setting is correct.
Summary of Contents for G3PW
Page 1: ...Cat No Z280 E1 01 User s Manual G3PW Power Controllers...
Page 2: ...G3PW Power Controllers User s Manual Produced November 2008...
Page 3: ...iv...
Page 15: ...xvi...
Page 49: ...34 Wiring for Specific Applications Section 3 4...
Page 61: ...46 Setting Parameters in the Initial Setting Level Section 4 6...
Page 77: ...62 Heater Burnout Detection Section 5 9...
Page 113: ...98 Parameter Settings in the Adjustment Level Appendix B...
Page 117: ...102 Index...
Page 119: ......