41
Procedures for Operation and Setting Parameters
Section 4-5
Parameter Settings
Operation Level
• The level when power is turned ON is the monitor level. Normal operation
is performed in the monitor level.
• Press the LVL Key to move to the adjustment level. In the adjustment
level, parameter settings can be changed during operation. Press the LVL
Key again to return to the monitor level.
• While in the monitor level or the adjustment level, press the LVL Key for at
least 2 s to move to the initial setting level. Then make the parameter set-
tings in the initial setting level. In this level, power to the load is turned
OFF.
• Press the LVL Key for at least 2 s to return to the monitor level from the
initial setting level. It is not possible to directly return to the adjustment
level from the initial setting level.
p
n
i
0
0
1
0
p
LVL
LVL
LVL
Power ON
Monitor level
Adjustment level
The ADJ indicator will light.
Initial setting level
The SET indicator will light.
(Press for at least 2 s.)
%(IN)
%(DIST)
%(OUT)
%(PHASE)
A
COMM
%(IN)
%(DIST)
%(OUT)
%(PHASE)
A
COMM
%(IN)
%(DIST)
%(OUT)
%(PHASE)
A
COMM
ADJ SET EV
ADJ SET EV
ADJ SET EV
The indicator for the unit will light.
(Press
for at
least 2 s.)
Summary of Contents for G3PW
Page 1: ...Cat No Z280 E1 01 User s Manual G3PW Power Controllers...
Page 2: ...G3PW Power Controllers User s Manual Produced November 2008...
Page 3: ...iv...
Page 15: ...xvi...
Page 49: ...34 Wiring for Specific Applications Section 3 4...
Page 61: ...46 Setting Parameters in the Initial Setting Level Section 4 6...
Page 77: ...62 Heater Burnout Detection Section 5 9...
Page 113: ...98 Parameter Settings in the Adjustment Level Appendix B...
Page 117: ...102 Index...
Page 119: ......