57
Monitoring Total Run Time
Section 5-8
5-8
Monitoring Total Run Time
The total run time monitor function is used to calculate the total time that
power is ON to the G3PW Power Controller and to output an alarm when the
time reaches the preset value in the Total Run Time Alarm Set Value parame-
ter [P16]. This function can be used for maintenance and managing equip-
ment by presetting replacement times for devices, such as heaters, in the
Total Run Time Alarm Set Value parameter.
Operation during an alarm output is set in the Total Run Time Exceeded
Operation parameter [P15] in the initial setting level.
The total run time exceeded alarm is set in the Total Run Time Alarm Set
Value parameter [P16] in the initial setting level.
The total run time is cleared by the Initialize Set Values parameter [P27] in the
initial setting level.
Use the Total Run Time Monitor parameter (POT) in the monitor level to mon-
itor the present total run time.
P15 setting
Meaning
0
No operation
The alarm does not operate.
1
Alarm level 1
An alarm is output to the ALARM1 contacts and operation is
stopped.
2
Alarm level 2
An alarm is output to the ALARM2 contacts and operation
continues.
P16 setting range
0.0 to 99.9 kh (0.0: Operation stopped)
P27 setting
Meaning
0
Do not initialize.
1
Initialize
Summary of Contents for G3PW
Page 1: ...Cat No Z280 E1 01 User s Manual G3PW Power Controllers...
Page 2: ...G3PW Power Controllers User s Manual Produced November 2008...
Page 3: ...iv...
Page 15: ...xvi...
Page 49: ...34 Wiring for Specific Applications Section 3 4...
Page 61: ...46 Setting Parameters in the Initial Setting Level Section 4 6...
Page 77: ...62 Heater Burnout Detection Section 5 9...
Page 113: ...98 Parameter Settings in the Adjustment Level Appendix B...
Page 117: ...102 Index...
Page 119: ......