Output Limits
Section 5-5
5-5
Output Limits
The output limit function can be used to set upper and lower limits for the out-
put value. The output value is found with the following formula:
Output value = Duty setting
×
Input value + Base-up value
The output limit is set in the Output Upper Limit (OLU) and Output Lower Limit
(OLL) parameters in the adjustment level, from 0.0% to 100% in each case.
If the output lower limit is set higher than the output upper limit, then the out-
put lower limit will be used as the output upper limit, and the output upper limit
will be used as the output lower limit. In other words, the higher value will
always be taken as the upper limit, and the lower value will always be taken as
the lower limit.
Parameter
Setting range (%)
Default (%)
Output Upper Limit (A06)
0.0 to 100
100
Output Lower Limit (A07)
0.0 to 100
0.0
100
0
100
50
Output value (%)
Output upper limit: 80%
Output lower limit: 20%
Input value (%)