![Omron G3PW User Manual Download Page 70](http://html1.mh-extra.com/html/omron/g3pw/g3pw_user-manual_742699070.webp)
55
Soft-start Up and Soft-start Down Functions
Section 5-6
5-6
Soft-start Up and Soft-start Down Functions
The soft-start up and soft-start down functions are used to change the output
value gradually within a set rate of change, even when the input value
changes suddenly. You can set the time for the output value to go from 0% to
100% (i.e., the SUP (soft-start up time)) and the time for the output value to go
from 100% to 0% (i.e., the SDN (soft-start down time)) to a value from 0.0 to
99.9 s.
• Relationships between Input and Output Values and Soft-start Up and
Down Times
!Caution
Specify the soft-start up time so that the inrush current will not be too large. If
the soft-start up time is set too low, the inrush current cannot be suppressed
and the load may be damaged.
Parameter
Setting range (s)
Default (s)
Meaning
Soft-start Up Time
(SUP)
0.0 to 99.9
0.5
The time for the output value
to go from 0% to 100%.
Soft-start Down
Time (SDN)
0.0 to 99.9
0.0
The time for the output value
to go from 100% to 0%.
100
Input value (%)
Output value (%)
Soft-start up time
Soft-start down time
Time
Time
0
100%
0%
Summary of Contents for G3PW
Page 1: ...Cat No Z280 E1 01 User s Manual G3PW Power Controllers...
Page 2: ...G3PW Power Controllers User s Manual Produced November 2008...
Page 3: ...iv...
Page 15: ...xvi...
Page 49: ...34 Wiring for Specific Applications Section 3 4...
Page 61: ...46 Setting Parameters in the Initial Setting Level Section 4 6...
Page 77: ...62 Heater Burnout Detection Section 5 9...
Page 113: ...98 Parameter Settings in the Adjustment Level Appendix B...
Page 117: ...102 Index...
Page 119: ......