Specifications
Section 2-1
2-1
Specifications
Specifications
Item
Standard Models
Constant-current Models
Model
G3PW-A2
@@
EU-
@
G3PW-A2
@@
EC-
@
-FLK
Control method
Analog input: Phase control or optimum cycle control
Voltage ON/OFF input: ON/OFF control
Maximum load capacity
• Phase control: Linear (resistive) load, transformer primary-side control
(Magnetic flux density: 1.25 T max.)
• Optimum cycle control: Linear (resistive) load (Transformer primary-side
control is not supported.)
Output
mode
Analog input
Phase
control
Proportional to phase angle (same
as G3PX), proportional to square
voltage, proportional to voltage
Proportional to phase angle (same
as G3PX), proportional to square
voltage, proportional to voltage, con-
stant-current control
Optimum
cycle
control
Optimum cycle control (Output is switched to 100% or 0% each half
cycle.)
Voltage ON/OFF
input
ON/OFF
control
Proportional to voltage control
Phase
Single
Rated voltage
100 to 240 VAC
Operating voltage range
−
15% to +10%
Power supply frequency
50/60 Hz
Power supply frequency fluctuation
±
3 Hz
Load current
-A220E
@
1 to 20 A
-A245E
@
1 to 45 A
-A260E
@
1 to 60 A
Inrush current
resistance
-A220E
@
220 A (60 Hz, 1 cycle)
-A245E
@
440 A (60 Hz, 1 cycle)
-A260E
@
440 A (60 Hz, 1 cycle)
Output voltage adjustable range
0% to 98%
Input signal for
control
Analog input
4 to 20 mA DC (input impedance: 100
Ω
) or 1 to 5 VDC (input impedance:
30.1 k
Ω
)
Voltage ON/OFF Input
5 VDC (input impedance: 30.1 k
Ω
)
External main setting
Specified Variable Resistor: G32X-V2K (2 k
Ω
, 2 W)
External duty setting
Output value
setting range
Main setting
0.0 to 100%
Base-up value
0.0 to 100% (Default: 0.0%)
Upper/ lower limits
Output upper limit: 0.0% to 100% (Default: 100%)
Output lower limit: 0.0% to 100% (Default: 0.0%)
Duty setting
Duty setting = Internal duty setting x External duty setting
Internal duty setting range (set using front-panel keys or communica-
tions): 0% to 100% (Default: 100%)
External duty setting range (set using external variable resistor): 0% to
100% (Default: 100%)
Soft-start up time and soft-start down time
0.0 to 99.9 s (Default: 0.5 s)
Either phase control or optimum cycle control can be used.
Constant current
---
Current fluctuation:
±
2% FS
Load current upper limit
---
0.0 to 66.0 (Default: 0.0 = OFF)
Overcurrent detection time: 500 ms
max.
Summary of Contents for G3PW
Page 1: ...Cat No Z280 E1 01 User s Manual G3PW Power Controllers...
Page 2: ...G3PW Power Controllers User s Manual Produced November 2008...
Page 3: ...iv...
Page 15: ...xvi...
Page 49: ...34 Wiring for Specific Applications Section 3 4...
Page 61: ...46 Setting Parameters in the Initial Setting Level Section 4 6...
Page 77: ...62 Heater Burnout Detection Section 5 9...
Page 113: ...98 Parameter Settings in the Adjustment Level Appendix B...
Page 117: ...102 Index...
Page 119: ......