82
Operation Command
Section 6-7
6-7
Operation Command
This command is used to start and stop operation, save the manipulated vari-
able, execute a software reset, or initialize settings.
Command
Response
Operation Codes and
Related Information
Note
(1) Execute a software reset to go from Initial Setting Level to Monitor Level.
(2) To use operation code 09, switching between automatic and manual for
the main setting must not be assigned to an event input (i.e., [P11] must
not be set to 2). Always set [P11] to 0 before using this operation code.
An operation error will occur if [P11] is set to 0.
(3) To use operation code 0A, switching the control method not be assigned
to an event input (i.e., [P11] must not be set to 1). Always set [P11] to 0
before using this operation code. An operation error will occur if [P11] is
set to 0.
(4) Parameters and the total time can be initialized only in Initial Setting Lev-
el.
(5) Execute an error reset to release the pause.
Response Codes
Example: The following command executes a software reset.
Command: [STX]0100030050600[ETX][BCC]
Response: None
"05"
Related
information
MRC
2
SRC
2
"30"
2
2
Operation
code
"05"
MRC
2
SRC
2
Response code
"30"
4
Operation
code
Operation
Related information
“06”
Software Reset
Always 00.
“07”
Setting Level Change (See note 1.)
00: Display level other than
Initial Setting Level
01: Display Initial Setting Level
“09”
Main Setting Automatic/Manual Selec-
tion (See note 2.)
00: Automatic
01: Manual
“0A”
Control Method Selection (See note 3.) 00: Phase control
01: Optimum cycle control
“0B”
Parameter Initialization (See note 4.)
Always 00.
“0C”
Error Reset
Always 00.
“0D”
Total Time Initialization (See note 4.)
Always 00.
“0F”
Pause (See note 5.)
Always 00.
Response code
Error name
Cause
“1001”
Command length too long
The command is too long.
“1002”
Command length too short
The command is too short.
“1100”
Parameter error
The operation code or related information is not correct.
“2203”
Operation error
An error occurred in nonvolatile memory.
“0000”
Normal end
Processing was completed normally.
Summary of Contents for G3PW
Page 1: ...Cat No Z280 E1 01 User s Manual G3PW Power Controllers...
Page 2: ...G3PW Power Controllers User s Manual Produced November 2008...
Page 3: ...iv...
Page 15: ...xvi...
Page 49: ...34 Wiring for Specific Applications Section 3 4...
Page 61: ...46 Setting Parameters in the Initial Setting Level Section 4 6...
Page 77: ...62 Heater Burnout Detection Section 5 9...
Page 113: ...98 Parameter Settings in the Adjustment Level Appendix B...
Page 117: ...102 Index...
Page 119: ......