Installation Environment
Section 3-1
■
Current-temperature Characteristic (G3PW-A260E)
• At least 20 mm must be provided on the left and right sides of the G3PW-
A260E. Refer to 3-2 Installation. If you must use side-by-side mounting,
then reduce the maximum load current when the ambient temperature is
over 30
°
C.
• Certification for safety standards was obtained with a mounting interval of
20 mm.
• Leave sufficient space for ventilation.
• Do not install the Power Controller above devices that generate significant
amounts of heat, such as heaters, transformers, and high-capacity resis-
tors.
• If the ambient temperature reaches 55
°
C or higher, install an air condi-
tioner to lower the temperature.
Note
If more than one Power Controller is installed side-by-side or vertically, the
heat that is generated will cause the internal temperatures of the Power Con-
trollers to rise and will shorten their service life. Take suitable measures, such
as installing fans for forced-air cooling.
Improving Noise
Immunity
• Do not install the Power Controller in a control panel together with high-
voltage devices.
• Install the Power Controller at least 200 mm away from power lines.
■
Recommended External Noise Filter
We recommend installing a noise filter on the primary side to improve noise
immunity.
Recommended filter: RSMN-series Filters from TDK-Lambda Corporation
RSMN-2030: For 20 A
RSMN-2060: For 45/60 A
Refer to 3-3-5 Wiring an External Noise Filter for wiring methods.
A
B
A
: Installation with 20 mm
between Power Controllers
B
: Close mounting
Load current (%)
100
80
60
40
20
0
10
20
30
40
50 55 60
Ambient temperature (
°
C)
Summary of Contents for G3PW
Page 1: ...Cat No Z280 E1 01 User s Manual G3PW Power Controllers...
Page 2: ...G3PW Power Controllers User s Manual Produced November 2008...
Page 3: ...iv...
Page 15: ...xvi...
Page 49: ...34 Wiring for Specific Applications Section 3 4...
Page 61: ...46 Setting Parameters in the Initial Setting Level Section 4 6...
Page 77: ...62 Heater Burnout Detection Section 5 9...
Page 113: ...98 Parameter Settings in the Adjustment Level Appendix B...
Page 117: ...102 Index...
Page 119: ......