38
Monitored Items
Section 4-3
4-3
Monitored Items
Values for the following five items can be monitored on the 7-segment display
during operation in monitor level.
■
Input Value (%)
The main setting that was set by automatic or manual input is displayed.
■
Duty Value (%)
The duty calculated from the internal and external duty settings is displayed.
Duty value (%) = Internal duty setting (%)
×
External duty setting (%)
■
Output Value (%)
The output value in relation to the input value is displayed after applying the
base-up value, output limits, soft-start up/down settings, and load current limit.
If no processing is performed, the output value will be the same as the input
value.
■
Output Phase Angle (%)
The thyristor module output phase angle (%) calculated from the output value
is displayed according to the output mode. When the proportional to phase
angle mode is used as the output mode, the output value and the output
phase angle will be the same.
■
Load Current (A)
The load current (A) detected by the built-in CT is displayed. This feature is
supported for Constant-current Models only.
Figure 1 Signal Flow Diagram (for Other than ON/OFF Control)
Duty Setting
1
0#
0#
CT
Automatic setting
Main Setting
0#
1
1
0#
1
4 to 20 mA
1 to 5 V
Communi-
cations
[P03] Input
Digital Filter
[P05] Main Setting Au-
tomatic Input Selection
Automatic/man-
ual selection
event
Base-up value
(Key Input)
Output upper/
lower limits
Input
value
[P08] Main Setting
Automatic/Manual
Default
Output limit
Soft-start
up/down
Manual setting
Variable
resistor
Variable
resistor
Key input
[P03] Input
Digital Filter
[P06] Main Set-
ting Manual Input
Selection
[P01] External
Duty Input Ena-
ble/Disable
Duty value
Internal duty
External duty
Key/com-
munications
[P03] Input
Digital Filter
Constant-current Models only.
Load Current
Upper Limit
Load current
limit processing
Output
value
Output phase
angle calcu-
lation
Output
phase angle
Thyristor
control cir-
cuit
Load
Load
current
#: Default
Summary of Contents for G3PW
Page 1: ...Cat No Z280 E1 01 User s Manual G3PW Power Controllers...
Page 2: ...G3PW Power Controllers User s Manual Produced November 2008...
Page 3: ...iv...
Page 15: ...xvi...
Page 49: ...34 Wiring for Specific Applications Section 3 4...
Page 61: ...46 Setting Parameters in the Initial Setting Level Section 4 6...
Page 77: ...62 Heater Burnout Detection Section 5 9...
Page 113: ...98 Parameter Settings in the Adjustment Level Appendix B...
Page 117: ...102 Index...
Page 119: ......