Appendix B
Parameter Settings in the Adjustment Level
*
1
Constant-current Models only.
Display
Name
Description
inp
(INP)
Key Input Main Set-
ting
Sets the input value.
0.0% to 100% (Default: 0.0)
dty
(DTY)
Internal Duty Setting
Sets the proportion of the input value to the output value as a duty.
0.0% to 100% (Default: 100)
bup
(BUP)
Base-Up Value
Sets the amount to increase the output value so that the output value does not go
to 0% even when the input value is 0%.
0.0% to 100% (Default: 0.0)
sup
(SUP)
Soft-start Up Time
Sets the time (from 0% to 100%) for increasing the output value gradually even
when the input value increases suddenly.
0.0 to 99.9 s (Default: 0.5)
sdn
(SDN)
Soft-start Down Time
Sets the time (from 100% to 0%) for decreasing the output value gradually even
when the input value decreases suddenly.
0.0 to 99.9 s (Default: 0.0)
olu
(OLU)
Output Upper Limit
Sets the output upper limit.
0.0% to 100% (Default: 100.0)
(If the output upper limit is set lower than the output lower limit, then the output
upper limit will be treated as the output lower limit.)
oll
(OLL)
Output Lower Limit
Sets the output lower limit.
0.0% to 100% (Default: 0.0)
(If the output lower limit is set higher than the output upper limit, then the output
lower limit will be treated as the output upper limit.)
hbr
(HBR)
Heater Burnout
Threshold
*
1
Sets the criteria for the heater burnout alarm output.
1% to 100% (Default: 100)
typ
(TYP)
Control Method
Sets the control method.
0: Phase control (Default)
1: Optimum cycle control
a-m
(A-m)
Main Setting Auto-
matic/Manual
Sets automatic or manual operation for the main setting.
0: Automatic (Default)
1: Manual
tpc
(TPC)
Teach Heater Char-
acteristics for Phase
Control
*
1
This parameter is displayed only when the control method is set to phase control.
It is used to record heater characteristics (resistance, output value/output phase
angle) for phase control.
hpr
(HPR)
Heater Characteristic
Resistance for Phase
Control
*
1
This parameter is displayed only when the control method is set to phase control.
It is used to check and correct the heater characteristic resistance set by teaching.
0.0 to 99.9
Ω
(Default: 0.0)
tcc
(TCC)
Teach Heater Char-
acteristics for Opti-
mum Cycle Control
*
1
This parameter is displayed only when the control method is set to optimum cycle
control. It is used to record the heater characteristics (resistance) for optimum
cycle control.
hcr
(HCR)
Heater Characteristic
Resistance for Opti-
mum Cycle Control
*
1
This parameter is displayed only when the control method is set to optimum cycle
control. It is used to check and correct the heater characteristic resistance set by
teaching.
0.0 to 99.9
Ω
(Default: 0.0)
hbl
(HBL)
Heater Burnout
Detection Lower
Limit
*
1
Sets the lower limit of the output value for judging heater burnout.
0.0% to 100% (Default: 0.0)
pot
(POT)
Total Run Time Moni-
tor
Displays the total time power is turned ON to the Power Controller in units of
0.1 kh.
0.0 to 99.9 (Default: 0.0 (function disabled))
Summary of Contents for G3PW
Page 1: ...Cat No Z280 E1 01 User s Manual G3PW Power Controllers...
Page 2: ...G3PW Power Controllers User s Manual Produced November 2008...
Page 3: ...iv...
Page 15: ...xvi...
Page 49: ...34 Wiring for Specific Applications Section 3 4...
Page 61: ...46 Setting Parameters in the Initial Setting Level Section 4 6...
Page 77: ...62 Heater Burnout Detection Section 5 9...
Page 113: ...98 Parameter Settings in the Adjustment Level Appendix B...
Page 117: ...102 Index...
Page 119: ......