77
Services and Addresses
Section 6-4
Variable Type C1/81 (Adjustment Level Parameters)
Note
Use address 0000 to set the communications main setting (input variable)
from the PLC.
Variable Type C3/83
Address
Data
Data range
Notation
0000
Communications Main Setting
H’00000000 to H’000003E8
The data range is ten times
the actual values.
0001
Communications Main Setting
0002
Communications Main Setting
0003
Communications Main Setting
0004
Communications Main Setting
0005
Communications Main Setting
0006
Communications Main Setting
0007
Communications Main Setting
0008
Internal Duty Setting
H’00000000 to H’000003E8
0009
Base-Up Value
H’00000000 to H’000003E8
000A
Soft-start Up Time
H’00000000 to H’000003E7
000B
Soft-start Down Time
H’00000000 to H’000003E7
000C
Output Upper Limit
H’00000000 to H’000003E8
000D
Output Lower Limit
H’00000000 to H’000003E8
000E
Heater Burnout Threshold
H’00000001 to H’00000064
---
000F
Heater Characteristic Resistance for Phase
Control
H’00000000 to H’000003E7
The data range is ten times
the actual values.
0010
Heater Characteristic Resistance for Opti-
mum Cycle Control
H’00000000 to H’000003E7
0011
Heater Burnout Detection Lower Limit
H’00000000 to H’000003E8
Address
Data
Data range
Notation
0000
Communications Data
Length
H’00000000 or H’00000001
0: 7 bits
1: 8 bits
0001
Communications Stop Bits
H’00000000 or H’00000001
0: 1 bit
1: 2 bits
0002
Communications Parity
H’00000000 to H’00000002
0: None
1: Even
2: Odd
0003
Send Wait Time
H’00000000 to H’00000063
0 to 99 ms
0004
Communications Timeout
Time
H’00000000 to H’000003E7
0: Communications timeout function disabled
0 to 999 s
0005
Communications Unit
Number
H’00000000 to H’00000063
0 to 99
0006
Communications Baud
Rate
H’00000000 to H’00000003
0: 9.6 k bit/s
1: 19.2 k bit/s
2: 38.4 k bit/s
3: 57.6 k bit/s
Summary of Contents for G3PW
Page 1: ...Cat No Z280 E1 01 User s Manual G3PW Power Controllers...
Page 2: ...G3PW Power Controllers User s Manual Produced November 2008...
Page 3: ...iv...
Page 15: ...xvi...
Page 49: ...34 Wiring for Specific Applications Section 3 4...
Page 61: ...46 Setting Parameters in the Initial Setting Level Section 4 6...
Page 77: ...62 Heater Burnout Detection Section 5 9...
Page 113: ...98 Parameter Settings in the Adjustment Level Appendix B...
Page 117: ...102 Index...
Page 119: ......