![Omron G3PW User Manual Download Page 59](http://html1.mh-extra.com/html/omron/g3pw/g3pw_user-manual_742699059.webp)
44
Setting Parameters in the Initial Setting Level
Section 4-6
Parameter Settings Related to Auxiliary Inputs
Main Setting Input Parameter Settings
The following table shows the relationship between the parameters related to
inputting the main settings.
or
External Duty Input Enable/Disable
[P01]
Output mode
Proportional to
phase angle
(same as G3PX)
Proportional to
square voltage
Proportional
to voltage
Constant-
current control
Optimum cycle
control
ON/OFF control
Parameter
Internal Duty only
[P01] = 0#
or
Setting enabled by external variable resistor.
[P01] = 1
Set the Input Digital Filter
Time Constant.
0.0 to 100 ms
[P03] = 0.0#
or
Input Digital Filter Time Constant
[P03]
Event Input Assignment
[P11]
No Assignment
[P11] = 0#
Phase Control and Optimum
Cycle Control Selection
[P11] = 1
Main Setting
Automatic/Manual Selection
[P11] = 2
To settings related to protective functions
#: Default
*: Setting disabled
Main Setting
Automatic Input
Selection [P05]
Main Setting
Manual Input
Selection [P06]
Event Input
Assignment
[P11]
0 (No assignment)
or
1 (Control method
selection)
Main Setting
Automatic/
Manual
Default [P08]
0 (Automatic)
Main setting input using
linear input or commu-
nications.
0 (4 to 20 mA or 1 to
5 V)
---
1 (Communications)
---
1 (Manual)
Main setting input using
an external variable
resistor or using key
operation.
---
0 (External variable
resistor)
---
1 (Key input)
2 (Main setting
automatic/manual
selection)
Event input
Open (Automatic)
0 (4 to 20 mA or 1 to
5 V)
---
1 (Communications)
---
Event input
Closed (Manual)
---
0 (External variable
resistor)
---
1 (Key input)
Summary of Contents for G3PW
Page 1: ...Cat No Z280 E1 01 User s Manual G3PW Power Controllers...
Page 2: ...G3PW Power Controllers User s Manual Produced November 2008...
Page 3: ...iv...
Page 15: ...xvi...
Page 49: ...34 Wiring for Specific Applications Section 3 4...
Page 61: ...46 Setting Parameters in the Initial Setting Level Section 4 6...
Page 77: ...62 Heater Burnout Detection Section 5 9...
Page 113: ...98 Parameter Settings in the Adjustment Level Appendix B...
Page 117: ...102 Index...
Page 119: ......