Moving  object  teaching  is  performed  by  using  more  than  one
object.  Perform  this  teaching  if  the  sensing  objects  cannot  be
stopped.  After  M̲TEACH  signal  input,  this  teaching  requires  six
processes  in  synchronization  with  external  trigger  input.  The
Sensor  will  not  be  in  detection  operation  during  the  teaching
process.  External  trigger  input  is  ignored  after  it  turned  ON  six
times.

1. Provide external M̲TEACH signal input.
2. Check that the ENAB signal is OFF.
3.  Provide  TRIG  signal  input  in  synchronization  with  the  measurement

timing of the sensing objects used for teaching.

4. Repeat step 3 six times.
5.  After  teaching  is  completed,  the  ENAB  signal  will  turn  ON.  At  that

time, check the status of the OUTPUT signal.

6. The OUTPUT signal will be ON if teaching is successfully completed.
7. The OUTPUT signal will be OFF if teaching is unsuccessful.
8. Turn the M̲TEACH signal OFF to complete the teaching process. If

the  teaching  has  been  unsuccessful,  the  Sensor  will  remain  in  the
previous  status.  Therefore,  perform  teaching  again.  The  teaching
operation  will  be  disabled  if  the  M̲TEACH  signal  is  turned  OFF
during the teaching process.

31

6.

External Teaching in RUN Mode 

Stationary object teaching is performed with the TRIG signal input 
or CONT signal input after external S̲TEACH signal input.
Therefore, do not move the object until teaching is completed.

1. Provide S̲TEACH signal input.
2. Check that the ENAB signal is OFF.
3.  Check  that  the  stationary  object  is  in  the  teaching  area  (or  in  the

sensing area if A.TEACH is set to ON).

4. Provide external CONT or TRIG signal input.
5.  After  teaching  is  completed,  the  ENAB  signal  will  turn  ON.  At  that

time, check the status of the OUTPUT signal.

6. The OUTPUT signal will be ON if teaching is successfully completed.
7. The OUTPUT signal will be OFF if teaching is unsuccessful.
8.  Turn  the  S̲TEACH  signal  OFF  to  complete  the  teaching  process.  If

teaching  has  been  unsuccessful,  the  Sensor  will  remain  in  the
previous status. Therefore, perform teaching again.

Teaching in process

Min 50ms

Repeat TRIG input

ON 
OFF
ON 
OFF

ON 
OFF

ON 
OFF

M_TEACH

TRIG

ENAB

OUTPUT

●Moving Object Teaching(M̲TEACH) 

In RUN mode, a model can be registered by external signal input 
using either of the following methods.

The data of the model is stored in the EEPROM when the teaching process 
of the Sensor completes. Therefore, do not turn OFF the Sensor during the 
teaching process. 
If  the  Sensor  is  turned  OFF,  an  EEPROM  data  error  will  result  when  the 
Sensor  is  turned  ON  again.  In  this  case,  perform  proper  teaching  and 
threshold level adjustments again.

ON 

OFF

ON 

OFF

ON 

OFF

ON 

OFF

S_TEACH

CONT or TRIG

ENAB

OUTPUT

Teaching in Process

●Stationary Object Teaching(S̲TEACH) 

approx.160ms

形F10-C20/C25/C30/C35/C50/C55    02.11.19  10:12  AM    ページ 31

Summary of Contents for F10-C20

Page 1: ...erved Thank you for selecting OMRON product This sheet primarily describes precautions required in installing and operating the product Before operating the product read the sheet thoroughly to acquir...

Page 2: ...he limitations of the ratings and functions Also take countermeasures for safety precautions such as fail safe installations Use under the circumstances or environment which are not described in the i...

Page 3: ...r motors are wired close to the Amplifier make sure that the Amplifier operates normally and take proper measures so that the power lines will not have a bad influence on the operation of the Amplifie...

Page 4: ...ms in normal wide and 10 8 ms in wide mode continuous measurement 1 model 1 bank Concord output Output turns ON if being concordant with registered model Discord output Output turns ON if not being co...

Page 5: ...1200bps 2400bps 4800bps 9600bps 19200bps 38400bps default 8bits Non 1bit CR Non RS 422 31 max with using Link Adapter F10 VR2 RS 232C or F10 VR4 RS 422 Serial Communication Interface only F10 C50 C55...

Page 6: ...MON Monitor Mode RUN Run Mode 7 F10 C30 C35 C50 C55 Pattern measurement Degree of conformity with model Plain measurement Contrast Plain measurement Average density F10 C20 C25 PATT Pattern measureme...

Page 7: ...slightly outside the detection range it may not be correctly taught Make sure the pattern is as close as possible to the center of the detection range OK Teaching status Plain Plain NG Color NG Stain...

Page 8: ...for the Unit for changing procedure RS 232C 422 A T ON A T OFF NM TMR LINE WD All the DIP switch pins are set to OFF at the factory Model Size WD Wide mode NM Normal mode Normal mode Wide mode Detecti...

Page 9: ...ot connected to the interior or casing We recommend using OMRON s S82K 01524 Power Supply F10 C20 NPN Models Level in dioatora 8 level green LEDs Black Orange OUTPUT ENAB S TEACH M TEACH TRIG CONT DC2...

Page 10: ...indicators 7 level red LEDs We recommend using OMRON s S82K 01524 Power Supply F10 C30 C50 NPN Models Note Ground or connect the shielded cable to 0V The shield is not connected to the interior or cas...

Page 11: ...0 C30 C35 C50 C55 Signal OUTPUT ENAB S TEACH M TEACH TRIG CONT BANK1 BANK2 BANK3 Control output Enabled output Stationary object teaching input Moving object teaching input Measurement trigger input C...

Page 12: ...ctor Multidrop Connections F10 C50 C55 F10 C50 C55 F10 C50 C55 Link Adapter Branching Link Adapter Branching Link Adapter Branching Link Adapter F10 VR4 RS 422 Cable F10 VR4 RS 422 Cable F10 VR4 RS 42...

Page 13: ...sensing object in the sensing area 6 Measurement Items PATT BANK 5 1 TEACH Mode Set the mode selector to TEACH Set the measurement item bank number selection switch to PATT BANK Bank No 0 will be dis...

Page 14: ...Measurement item selection level By another mode it is possible to enlarge Detection Range Upper Detection Range Detection Range Detection Range Detection Range 8 7 6 5 4 3 2 1 Deviation High Low A D...

Page 15: ...nt Detection range at Plain Measurement is as following Mode 1 and 2 can be changed by the operation at the power supply input Plain Measurement detection range selection mode Mode 1 Initial setting M...

Page 16: ...monitoring the level indicator Altered threshold values will not be saved unless the mode selector is changed once to either RUN or TEACH 8 7 6 5 4 3 2 1 8 7 6 5 4 3 2 1 Plain Measurement Press the t...

Page 17: ...OUTPUT signal is refreshed 5 3 RUN Mode Set the mode selector to RUN When the switch is set to RUN mode measurements are made in response to external input signals 1 Relationship between the F10 I O t...

Page 18: ...while measuring Measuring Measuring Please restart the measurement process after confirming that the ENAB output is ON The measurement is finished after CONT signal input is OFF And then F10 check the...

Page 19: ...S TEACH signal input Therefore do not move the object until teaching is completed 1 Provide S TEACH signal input 2 Check that the ENAB signal is OFF 3 Check that the stationary object is in the teach...

Page 20: ...oo Please refer to the 7 4 Command Reference Ex Unit number 23 Do not turn off before pressing the teaching button otherwise the changed timer will not be registered 8 7 6 5 4 3 2 1 Lighting Level Ind...

Page 21: ...ector to TEACH while the power supply is turning off 2 Turn on the power supply while pushing the Teach display button 3 Release the Teach display button after confirming that the illumination of each...

Page 22: ...ed below Specify the header 40 at the beginning of input commands 1 byte fixed A value between 00 to 31 or XX can be set as the unit number 2 bytes When the unit number is a single digit it must be pr...

Page 23: ...ght 8 3 List of Input Commands Specifying F10 Operation The following commands specify the operation of the F10 such as executing a measurement changing the bank number etc Saving Loading data The fol...

Page 24: ...Output Response unit number BC OK CR Executed correctly unit number BC ER CR Not executed correctly unit number 00 to 31 Unit number of Unit to change Example To change the bank number of Unit 10 to...

Page 25: ...transfer all bank data from Unit 6 to the host Input 06BS AL CR Data will be transferred using the XMODEM protocol Output 06BS OK CR HT Head Type Acquire head type HT acquires the head type Input Comm...

Page 26: ...er Set the following numerical values for type Set the following numerical values for level Output Response unit number LS OK CR Executed correctly unit number LS ER CR Not executed correctly unit num...

Page 27: ...on result agreement agreement agreement CR Pattern measurement at 3 models Wide mode unit number MD ER CR Not executed correctly unit number Unit number 00 to 31 comparison result 0 Comparison result...

Page 28: ...e the image in memory once only and return the results by serial communications with Unit 27 in Plain Measurement Mode 49 comparison result contrast average density CR Plain measurement comparison res...

Page 29: ...Output Response unit number MM measurement mode CR Executed correctly unit number 00 to 31 Designated unit number measurement mode 0 Plain Measurement Mode 1 Pattern Measurement Mode 1 model 2 Patter...

Page 30: ...e unit number SG value CR Executed correctly unit number SG ER CR Not executed correctly unit number 00 to 31 Designated unit number parameter 0 Unit number value 01 to 31 Unit number parameter 1 Baud...

Page 31: ...NT or TRIG ON During teaching the ENAB signal will be ON 55 number for parameter cannot be specified Set the following numerical values for parameter and value After changing the unit number the previ...

Page 32: ...e Connect the Head and turn the Sensor OFF and ON Note If the same error occurs again the Head may be brok en Consult your OMRON represen tative This LED of the threshold indicators fla shes and the b...

Page 33: ...R S50R inseead Perform the teaching of the Sensor in TEACH mode All the LED of the threshold indicators fla shes and the buzzer sounds Serial buffer overflow er ror Either the send buffer or receive b...

Page 34: ...ations subject to change without notice OMRON Corporation 8 95 11 5 4 8 40 27 32 2 20 41 2000 150 4 15 24 99 8PIN CIRCULAR CONNECTOR F10 VR2 PLUG TYPE F10 VR4 SOCKET TYPE F10 C20 C25 C30 C35 C50 C55 0...

Page 35: ...Mouser Electronics Authorized Distributor Click to View Pricing Inventory Delivery Lifecycle Information Omron F10S30R...

Reviews: