E5AK
5--23
Input digital filter
·
Sets the time constant of the input digital filter. The following figures shows the effect
on data after passing through the digital filter.
A
PV before passing through filter
PV after passing through filter
0.63A
Input digital filter
Time
constant
Time
Setting Range
Unit
Default
0 to 9999
Second
0
Open/close hysteresis
Conditions of Use
Control must be position-proportional con-
trol.
·
Provides hysteresis at ON/OFF switching of open or close output in position-propor-
tional control.
Setting Range
Unit
Default
0.1 to 20.0
%
0.8
F
Related article
4.1 Selecting the Control Method/Position-proportional Control (page 4-3)