CHAPTER 5 PARAMETERS
E5AK
5--10
·
The parameters in this mode can be used only when the “security” parameter (pro-
tect mode) is set to “0” to “3”.
·
This mode contains the main parameters for adjusting control. These parameters
include parameters for executing AT (auto-tuning), setting the alarm values, setting
the control period, and setting PID parameters.
·
To select this mode when in the levels 0 and 2, setup, expansion, option and calibra-
tion modes, press the
key for 1 second minimum. The display changes to the
menu display. If you select [
] then press the
key for 1 second minimum, the
controller enters the level 1 mode.
·
To select parameters in this mode, press the
key. To change parameter settings,
use the
or
keys.
·
The following table shows the parameters supported in this mode and the page where
the parameter is described.
Symbol
Parameter Name
Page
AT Execute/Cancel
5-11
Set point 0
5-11
Set point 1
5-11
Set point 2
5-11
Set point 3
5-11
Alarm value 1
5-12
Alarm value 2
5-12
Alarm value 3
5-12
Proportional band
5-12
Integral time
5-12
Derivative time
5-12
Cooling coefficient
5-13
Dead band
5-14
Position-proportional dead band
5-14
Manual reset value
5-15
Hysteresis (heat)
5-15
Hysteresis (cool)
5-15
Control period (heat)
5-16
Control period (cool)
5-16
Heater current monitor
5-17
Heater burnout
5-17
Level 1 Mode