CHAPTER 5 PARAMETERS
E5AK
5--14
Dead band
Conditions of Use
The control system must be heating and
cooling control.
·
Sets the output dead band width in a heating and cooling control system. A negative
setting sets an overlap band.
Setting Range
Unit
Default
-19.99 to 99.99
%FS
0.00
F
Related article
4.1 Selecting the Control Method (page 4-2)
E5AK-AA2 AC100-240
E5AK-AA2 AC/DC24
Position-proportional
dead band
Conditions of Use
Control must be position-proportional con-
trol
·
Sets the output hold width during position-proportional control (ON/OFF switching
point for open and close output).
Open/close hysteresis
Dead band
MV--Valve opening
100%
0
-100%
OFF
ON
Setting Range
Unit
Default
0.1 to 10.0
%
2.0
F
Related article
4.1 Selecting the Control Method/Position-proportional Control (page 4-3).
F
Related parameter
“Open/close hysteresis” (Level 2 mode)