E5AK
5--39
Event input assignment 1
Event input assignment 2
Event input assignment 3
Event input assignment 4
Conditions of Use
Event input other than the multi-SP func-
tion must be specified when the event
input function is in use.
·
When one E53-AKB unit is mounted, only “Event input assignment 3” and “Event
input assignment 4” can be used.
·
This parameter specifies event input other than the multi-SP function. The following
four functions can be specified:
Run/Stop, Remote/Local, Auto/Manual, SP mode.
The Remote/Local function can be used on E53-AK01/02/03 option units. The SP
mode functions can be used only when the ”Remote SP enable” parameter is ON.
·
Event input (Run/Stop, Manual/Auto, and SP mode) is disabled while the menu is dis-
played.
It is also disabled in set up, expantion, option and calibration modes.
Symbol
Function
Event Input Operation
Not specified
Event input disabled
Run/Stop
ON: Stop/OFF: Run
Remote/Local
ON: Remote/OFF: Local
Manual/Auto
ON: Manual/OFF: Auto
SP mode
ON: Remote SP/OFF: Local SP
·
Default
E53-AKB
×
1
E53-AKB
×
2
Event input assignment 1
--
Event input assignment 2
--
Event input assignment 3
Event input assignment 4
F
Related article
4.3 How to Use Event input (page 4-8)
F
Related parameters
“remote SP enable” “multi-SP function” (option mode)
F
Option unit
E53-AKB
Option Mode
Function
Comment
See
Model