E5AK
5--13
Proportional band
Integral time
Derivative time
Conditions of Use
Control must be advanced PID control,
and ST must be set to OFF.
·
Sets the PID parameters. However, note that the PID parameter settings are changed
to optimum values when auto-tuning is executed, and self-tuning is selected.
Parameter
Setting Range
Unit
Default
Proportional band
0.1 to 999.9
%FS
10.0
Integral time
0 to 3999 (see note1)
Second
233
Derivative time
0 to 3999
Second
40
note1
: During position-proportional control, the setting range become 1 to 3999s.
F
Related parameter
“AT Execute/Cancel” (level 1 mode)
Cooling coefficient
Conditions of Use
The control must be either heating and
cooling control, or advanced PID control.
·
In heating and cooling control, P at the cooling side is calculated by the following for-
mula:
Cooling side P = cooling coefficient
¢
P
Setting Range
Unit
Default
0.01 to 99.99
None
1.00
F
Related article
4.1 Selecting the Control Method (page 4-2)
F
Related parameter
“Proportional band” (level 1 mode)
E5AK-AA2 AC100-240
E5AK-AA2 AC/DC24