2.3 Wiring Terminals
E5AK
2--9
·
Connect the sensor input to terminal Nos. 11 to 14 and 33 as follows
according to the input type.
14
13
12
11
33
14
13
12
11
33
14
13
12
11
33
14
13
12
11
33
--
+
--
+
--
+
mA
Thermocouple
Platinum
resistance
thermometer
Voltage input
Current input
V
·
Terminal Nos. 7 and 8 are for control output 1 (OUT1), and terminal Nos.
5 and 6 are for control output 2 (OUT2). The following diagrams show the
available output units and their internal equalizing circuits.
·
With E53-V
VV
output units, about 2 V is output for one second after the
power is interrupted.
·
The following table shows the specifications for each output unit.
Model
Output Type
Specifications
E53-R
Relay
250 VAC, 5 A
E53-S
SSR
75 to 250 VAC, 1 A
E53-Q
E53-Q3
E53-Q4
Voltage (NPN)
Voltage (NPN)
Voltage (PNP)
NPN : 12 VDC, 40 mA (with short-circuit protection)
NPN : 24 VDC, 20 mA (with short-circuit protection)
PNP : 24 VDC, 20 mA (with short-circuit protection)
E53-C3
E53-C3D
4 to 20 mA
0 to 20 mA
4 to 20 mA, Permissible load impedance: 600
W
max., Resolution: Approx. 2600
0 to 20 mA, Permissible load impedance: 600
W
max., Resolution: Approx. 2600
E53-V34
E53-V35
0 to 10 V
0 to 5 V
0 to 10 VDC, Permissible load impedance: 1 k
W
min., Resolution: Approx. 2600
0 to 5 VDC, Permissible load impedance: 1 k
W
min., Resolution: Approx. 2600
With E5AK-PRR2 controllers, relay output (250 VAC, 1 A) is fixed.When
replacing the output unit, use the E53-R. The following diagrams show the
relationship between terminals and open/close relay settings.
8
7
Open
6
5
Close
F
Sensor input
10
9
8
7
6
5
4
3
2
1
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
31 32
33
F
Control output
10
9
8
7
6
5
4
3
2
1
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
31 32
33