CHAPTER 5 PARAMETERS
E5AK
5--8
Set point during SP ramp
Conditions of Use
The remote SP function must be enabled.
When the remote SP function is disabled,
this function can be used only when the
SP ramp function is enabled.
·
Monitors the set point during SP ramp
·
Matches the set point of the “PV/SP” parameter when the set point is not during SP
ramp .
Moniter Range
Unit
Local SP : Local SP setting lower limit to local SP setting upper limit
EU
Remote SP : Remote SP lower limit to remote SP upper limit
EU
F
Related article
4.2 Operating Condition Restriction/SP ramp (page 4-6)
F
Related parameters
“PV/SP” (level 0 mode)
“SP ramp time unit” “SP ramp set value” (level 2 mode)
“Set point upper limit” “Set point lower limit” (expansion mode)
“SP mode” (level 2 mode)
“Remote SP enable” “Remote SP upper limit” “Remote SP lower limit” (option
mode)
MV monitor (heat)
MV monitor (cool)
Conditions of Use
Control must be standard control or heat-
ing and cooling control.
·
This parameter cannot be set.
·
Monitors the manipulated variable on the heating or cooling side.
·
The manipulated variable in a standard control system is checked in the “MV moni-
tor (heat)” parameter.
·
The “MV monitor (cool)” parameter can be used only during heating and cooling con-
trol.
·
MV monitor (heat)
Control
Monitor Range
Unit
Standard
-5.0 to 105.0
%
Heating and cooling
0.0 to 105.0
%
·
MV monitor (cool)
Control
Monitor Range
Unit
Heating and cooling
0.0 to 105.0
%
E5AK-AA2 AC100-240
E5AK-AA2 AC/DC24
Level 0 Mode
Function
Monitor
See
Function
Monitor
Model