CHAPTER 5 PARAMETERS
E5AK
5--44
Remote SP enable
Conditions of Use
ST must be OFF.
·
When this parameter is set to “ON”, the remote SP and local SP can be switched for
use. (That is, to the SP mode can be specified.). Also, the “set point during SP ramp”
parameter is enabled at all times.
·
When this parameter is set to “OFF”, only the local SP can be used. The set point dur-
ing SP ramp is enabled only when the SP ramp function is enabled.
Setting Range
Default
[
]: Enabled/[
]: Disabled
[
]
F
Related article
4.4 How to Use the Remote SP (page 4-11)
F
Related parameters
“Set point during SP ramp” (level 0 mode)
“SP mode” (level 2 mode)
Remote SP upper limit
Remote SP lower limit
Conditions of Use
The remote SP function must be enabled.
·
Sets the remote SP upper and lower limit values. The upper limit value is the equiva-
lent to 20 mA, and the lower limit value is equivalent to 4 mA. Set the upper limit
value in the “remote SP upper limit” parameter and the lower limit value in the
“remote SP lower limit” parameter.
RSP (%)
4
20
Input (mA)
Upper limit value
Lower limit value
·
When the “SP setting upper limit” or “SP setting lower limit” parameters are
changed, the remote SP upper and lower limit values are forcibly changed to the SP
setting upper and lower limit values.
Option Mode
Function
Comment
See
Function