6.4 Commands and Responses
E5AK
6--9
Parameter No.
Parameter
Data Setting Range
Mode
28
Set point upper limit
*1
Set point lower limit +1 to scaling upper limit
27
Set point lower limit
*1
Scaling lower limit to Set point upper limit -1
72
PID / ON/OFF
0: Advanced PID, 1: ON/OFF
73
ST
0 : OFF, 1 : ON
34
ST stable range width
0.1 to 999.9
35
a
0.00 to 1.00
Expansion
85
AT calculated gain
0.1 to 10.0
p
37
Standby sequence reset method
0, 1
36
Automatic return of display mode
0 to 99
93
AT hysteresis
0.1 to 9.9
55
LBA detection width
0.0 to 999.9
74
Multi-SP function
0 to 2
77
Event input assignment 3
--1 to 3
78
Event input assignment 4
--1 to 3
79
Transfer output type
0 to 5
81
Transfer output upper limit
80
Transfer output lower limit
82
HBA latch
0: OFF, 1: ON
Option
89
Travel time
1 to 999
p
38
PV dead band
0 to 9999
29
Remote SP enable
0: Enabled, 1: Disabled
91
Remote SP upper limit
SP setting lower limit to SP setting upper limit
90
Remote SP lower limit
SP setting lower limit to SP setting upper limit
39
SP tracking
0: OFF, 1: ON
*1 During temperature input, the range becomes the range of use of the selected sensor instead of the scaling upper/lower limit values
*2 See page 5-35.
*3 - -1: No specification, 0: Run/Stop, 1: Remote/Local, 2: Auto/Manual, 3: SP mode
*4 The following table shows the output ranges of the Transfer output lower and upper limits.
Transfer output Type
Transfer Output Lower Limit to
Transfer Output Upper Limit
0:
Set point
Set point lower limit value to Set point upper limit value
1:
Set point during SP ramp
Set point lower limit value to Set point upper limit value
2:
Process value
Scaling lower limit to scaling upper limit
3:
Manipulated variable (heat)
-5.0% to 105.0% (Standard control), 0.0 to 105.0% (heat-
ing and cooling control)
4:
Manipulated variable (cool)
0.0% to 105.0%
5:
Valve opening
-10.0 to 110.0%
*2
*3
*3
*4
*4
*4