6.4 Commands and Responses
E5AK
6--11
F
A group
Bit
Description
[1]
[0]
0
Heating side output
*3
ON
OFF
*1
1
Cooling side output
*4
ON
OFF
*1
2
Alarm output 1
ON
OFF
*2
3
Alarm output 2
ON
OFF
*2
4
Alarm output 3
ON
OFF
*2
5
LBA output
ON
OFF
*2
6
HBA output
ON
OFF
*2
7
Run/Stop
Stop
Run
8
Auto/Manual
Manual
Auto
9
Remote/Local
Remote
Local
10
SP mode
RSP
LSP
11
Auto-tuning
AT exection
OFF
12
13
14
Event input 3
ON
OFF
15
Event input 4
ON
OFF
*1 Always “OFF” at linear output
*2 Always “OFF” when output is not assigned
*3 During position-proportional control, output is Open.
*4 During position-proportional control, output is Close.
F
B group
Bit
Description
[1]
[0]
0
Setting level
1
0
1
RAM write mode
RAM
Backup
2
Control output 1 type
Linear
Pulse
3
Control output 2 type
Linear
Pulse
4
EEPROM
RAM
¸
EEPROM
RAM = EEPROM
5
Input error
ON
OFF
6
A/D converter error
ON
OFF
7
CT overflow
ON
OFF
8
CT hold
ON
OFF
9
Potentiometer error
ON
OFF
10
RSP input error
ON
OFF
11
12
13
14
15
To return to setting level 0 from setting level 1, issue the “software reset” command.
If the parameter write command is issued for the setup and expansion modes in set-
ting level 0, an error occurs, and the end code (0D = Command cannot be executed)
is returned.
About Setting Levels