6.4 Commands and Responses
E5AK
6--7
Parameter No.
Parameter
Data Setting and Monitor Range
Mode
00
PV monitor
*1
Scaling lower limit -10% to scaling upper limit +10%
86
SP monitor during SP
*1
ramp
SP lower limit to SP upper limit
04
MV monitor (heat)
*1
-5.0 to 105.0
L
l
42
MV monitor (cool)
*1
0.0 to 105.0
Level 0
24
Remote SP monitor
*1
Scaling lower limit to scaling upper limit
14
Valve opening monitor
*1
-10.0 to 110.0
01
Set point
SP lower limit to set point upper limit
10
Set point 0
SP lower limit to SP upper limit
11
Set point 1
SP lower limit to SP upper limit
12
Set point 2
SP lower limit to SP upper limit
13
Set point 3
SP lower limit to SP upper limit
02
Alarm value 1
-1999 to 9999
03
Alarm value 2
-1999 to 9999
41
Alarm value 3
-1999 to 9999
19
Proportional band
0.1 to 999.9
20
Integral time
0 to 3999
21
Derivative time
0 to 3999
22
Cooling coefficient
0.01 to 99.99
Level 1
09
Dead band
-19.99 to 99.99
87
Position-proportional dead
band
0.1 to 10.0
23
Manual reset value
0.0 to 100.0
06
Hysteresis (heat)
0.01 to 99.99
43
Hysteresis (cool)
0.01 to 99.99
07
Control period (heat)
1 to 99
08
Control period (cool)
1 to 99
17
Heater current monitor
*1
0.0 to 55.0
18
Heater burnout alarm
0.0 to 50.0
*1 Possible only during reading
*2 During temperature input, the range becomes the range of use of the selected sensor.
*3 During heating and cooling control, the range becomes 0.0 to 105.0.
*4 During position-proportional control, the range becomes 1 to 3999.
Currently, if a command is used for invalid parameters (parameters that do not sat-
isfy the conditions of use in Chapter 5), the “undefined” error (end code: 1C) is out-
put.
About invalid
parameters
*2
*3
*4