CHAPTER 1 INTRODUCTION
E5AK
1--6
Control outputs 1 and 2 are used depending on the differences in control
method as follows.
Control Method
Model
Control Output 1/
Control Output 2
Standard control
E5AK-AA2 AC100-240
E5AK-AA2 AC/DC24
Control output (heat) /
Alarm, etc.,
Heating and cooling
control
E5AK-AA2 AC100-240
E5AK-AA2 AC/DC24
Control output (heat) /
Control output (cool)
Position-proportional
control
E5AK-PRR2 AC100-240
E5AK-PRR2 AC/DC24
Open/Close
The E5AK supports the following six transfer outputs.
Set point
Set point during SP ramp
Process value
Heating side manipulated variable
Cooling side manipulated variable
Valve opening
However, note that heating/cooling side manipulated variables can be out-
put only standard type controllers, and valve opening can be output on
position-proportional type controllers
These transfer outputs can be output after being scaled. Setting of an
upper limit value smaller than the lower limit value is allowed, so reverse
scaling can also be carried out.
F
Transfer output