SETTING LIST
E5AK
A--9
Mode
Parameter Name
Setting Range
Unit
Default
Remarks
Setting
Input type
0 to 21
None
2
Scaling upper limit
Scaling lower limit +1 to 9999
EU
-100
Analog input
Scaling lower limit
-1999 to SP setting upper limit -0.1
EU
0
Analog input
Decimal point
0 to 3
None
0
Analog input
_
C/
_
F selection
_
C/
_
F
None
_
C
Temperature input
Parameter initialize
Yes/No
None
NO
Control output 1 assignment
Heat/Cool/Alarm 1/Alarm 2/Alarm 3
/HBA/LBA
None
HEAT
Control output 2 assignment
Heat/Cool/Alarm 1/Alarm 2/Alarm 3
/HBA/LBA
None
AL-1
Auxiliary output 1 assignment
Alarm 1/Alarm 2/Alarm 3/HBA/LBA/
S.ERR/E333/RSER
None
AL-2
Setup
Auxiliary output 2 assignment
Alarm 1/Alarm 2/Alarm 3/HBA/
LBA/S.ERR/E333/RSER
None
AL-3
Alarm 1 type
1 to 11
None
2
Output assignment
needed
Alarm 1 open in alarm
N-O/N-C
None
N-O
Output assignment
needed
Alarm 2 type
1 to 11
None
2
Output assignment
needed
Alarm 2 open in alarm
N-O/N-C
None
N-O
Output assignment
needed
Alarm 3 type
1 to 11
None
2
Output assignment
needed
Alarm 3 open in alarm
N-O/N-C
None
N-O
Output assignment
needed
Direct/Reverse operation
OR-R/OR-D
None
OR-R
Set point upper limit
Set point lower limit +1 to scaling
upper limit
None
1300
Set point lower limit
Scaling lower limit to Set point upper
limit -1
None
-200
PID/ON/OFF
PID / ON/OFF
None
PID
ST
OFF/ON
None
OFF
E
ST stable range
0.1 to 999.9
°
C/
°
F
15.0
ST=ON
Expan-
sion
a
0.00 to 1.00
None
0.65
sion
AT calculated gain
0.1 to 10.0
None
1.0
Standby sequence reset set-
ting method
0/1
None
0
Automatic return of display
mode
0 to 99
Sec
0
AT hysteresis
0.1 to 9.9
%FS
0.2
LBA detection width
0.0 to 999.9
%FS
0.2
*4 When temperature input is selected, the sensor range selected in the “input type” parameter (setup mode) corresponds to the scal-
ing upper and lower limit value.
*4
*4
*4
*2
*2
*4