E5AK
5--45
Parameter
Setting Range
Unit
Default
Remote SP upper limit SP setting lower limit to SP setting upper limit
EU
1300
Remote SP lower limit
SP setting lower limit to SP setting upper limit
EU
-200
F
Related article
4.4 How to Use the Remote SP (page 4-11)
F
Related parameters
“Decimal point” (setup mode)
“SP setting upper limit” “SP setting lower limit” (expansion mode)
“Remote SP enable” (option mode)
SP tracking enable
Conditions of Use
The remote SP function must be enabled.
·
Specifies the operation when the remote SP mode is switched to the local SP mode.
·
When this parameter is set to “ON”, the local SP is changed to the remote SP value
used immediately before switching.
·
When this parameter is set to “OFF”, the local SP is not influenced by the remote SP.
Setting Range
Default
[
]: Enabled/[
]: Disabled
[
]
F
Related article
4.4 How to Use the Remote SP (page 4-11)
F
Related parameters
“Set point during SP ramp” (level 0 mode)
“SP mode” (level 2 mode)
Option Mode
Comment
See
Function
Comment