CHAPTER 6 USING THE COMMUNICATIONS FUNCTION
E5AK
6--8
Parameter No.
Parameter
Data Setting Range
Mode
44
SP ramp time unit
0: Minutes, 1: Hours
45
SP ramp set value
0 to 9999
46
LBA detection time
0 to 9999
47
MV at stop
-5.0 to 105.0
48
MV at PV error
-5.0 to 105.0
50
MV upper limit
MV lower limit +0.1 to 105.0
49
MV lower limit
-5.0 to MV upper limit -0.1
51
MV change rate limit
0.0 to 100.0
Level 2
56
Input digital filter
0 to 9999
88
Open/close hysteresis
0.1 to 20.0
25
Alarm 1 hysteresis
0.01 to 99.99
26
Alarm 2 hysteresis
0.01 to 99.99
52
Alarm 3 hysteresis
0.01 to 99.99
53
Input shift upper limit
-199.9 to 999.9
54
Input shift lower limit
-199.9 to 999.9
57
Input type
0 to 21
59
Scaling upper limit
Scaling lower limit +1 to 9999
58
Scaling lower limit
-1999 to scaling upper limit -1
60
Decimal point
0 to 3
30
_
C/
_
F selection
0 :
_
C, 1 :
_
F
61
Control output 1 assignment
0 to 6
62
Control output 2 assignment
0 to 6
63
Auxiliary output 1 assignment
2 to 9
Setup
64
Auxiliary output 2 assignment
2 to 9
Setup
65
Alarm 1 type
1 to 11
66
Alarm 1 open in alarm
0: closed in alarm, 1: open in alarm
67
Alarm 2 type
1 to 11
68
Alarm 2 open in alarm
0: closed in alarm, 1: open in alarm
69
Alarm 3 type
1 to 11
70
Alarm 3 open in alarm
0: closed in alarm, 1: open in alarm
71
Direct/Reverse operation
0: Reverse operation, 1: Direct operation
*1 During heating and cooling control, the range becomes -105 to 105.0. During position-proportional control, you can select between
*1
0: Hold/1: Open/2: Close. (Default is 0: Hold.)
*2 During heating and cooling control, the range becomes 0.0 to 105.0.
*3 During heating and cooling control, the range becomes -105.0 to 0.0
*4 See page 5-26.
*5 0: Control output (heat), 1: Control output (cool), 2: to 4: Alarms 1 to 3, 5: HBA, 6: LBA, 7 to 9: Errors 1 to 3
*6 See page 5-30.
*1
*1
*2
*3
*4
*5
*5
*5
*5
*6
*6
*6