
E5AK
5--19
Remote/Local
Conditions of Use
The communications function must be in
use.
·
Switches between remote and local operation.
·
To change the parameter setting during remote operation, use the communications
function. To change the parameter setting during local operation, change the setting
on the E5AK controller.
You can check the parameter setting by both communications and on the E5AK con-
troller regardless of whether the controller is switched to remote or local operation.
·
When the event input to which “remote/local” is assigned is ON, the controller
switches to the remote mode. When the event input is OFF, the controller switches
to the local mode.
Setting Range
Default
[
]: remote / [
]: local
[
]
F
Related article
Chapter 6 Using the Communications Function
F
Related parameters
“Communication stop bit” “Communication data length” “Communication parity”
“Communication baud rate” “Communication unit No.” “Event input assignment
1” “Event input assignment 2” “Event input assignment 3” “Event input assign-
ment 4” (option mode)
F
Option units
E53-AK01/02/03
SP mode
Conditions of Use
The remote SP function must be enabled
and ST must be set to OFF.
·
Switches between remote SP and local SP.
·
Switches the SP to the remote SP when an event input to which the “SP mode” has
been assigned is ON. Switches the SP to the local SP when an event input to which
the “SP mode” has been assigned is OFF.
Setting Range
Default
[
]: Remote SP/[
]: Local SP
F
Related article
4.4 How to Use the Remote SP (page 4-11)
F
Related parameters
“Remote SP enable”
“Event input assignment 1” “Event input assignment 2” “Event input assignment
3” “Event input assignment 4” (option mode)
Level 2 Mode
Function
Comment
See
Model
Function
Comment
See