SPECIFICATIONS
E5AK
A--3
J
Characteristics
Indication Accuracy
Thermocouple:
(
±
0.3%
of indication value or ±
1
°
C, whichever greater)
±
1 digit max.
(*1)
Platinum resistance thermometer:
(
±
0.2% of indcation value or
±
0.8
°
C whichever greater)
±
1 digit max.
Analog input:
±
0.2%
±
1 digit max.
CT input:
5%FS
1 digit max.
Potentiometer:
5%FS
1 digit max.
Remote SP:
0.2%FS
1 digit max.
Hysteresis
0.01 to 99.99%FS (in units of 0.01%FS)
Proportional Band (P)
0.1 to 999.9% FS (in units of 0.1%FS)
Integral (reset) Time (I)
0 to 3999 s (in units of 1 second)
Derivative (rate) Time (D)
0 to 3999 s (in units of 1 second)
Control Period
1 to 99 s (in units of 1 second)
Manual Reset Value
0.0 to 100.0% (in units of 0.1%)
Alarm Setting Range
-1999 to 9999 or -199.9 to 999.9 (decimal point position dependent on input type
or result of scaling)
Sampling Period
Temperature input: 250 ms, Analog input: 100 ms, Sub-input : 1s
Insulation Resistance
20 M
W
min. (at 500 VDC)
Dielectric Strength
2000 VAC, 50/60Hz for 1 min (between terminals of different polarities)
Vibration
Malfunction 10 to 55 Hz, 10 m/s
2
(approx.1G) for 10 min each in X, Y, and Z directions
Vibration
Resistance
Destruction 10 to 55 Hz, 20 m/s
2
(approx.2G) for 2hrs each in X, Y, and Z directions
Shock Resis-
tance
Malfunction 200 m/s
2
min. (approx.20G), 3 times each in 6 directions (100 m/s
2
(approx.10G)
applied to the relay)
tance
Destruction 300 m/s
2
min. (approx.30G), 3 times each in 6 directions
Weight
Approx. 450 g, mounting bracket: approx. 65 g
Enclosure Ratings
Front panel: NEMA4 for indoor use (equivalent to IP66)
Rear case: IEC standard IP20
Terminals: IEC standard IP00
Memory Protection
Non-volatile memory (number of writings:100000 operations)
*1The indication accuracy of the K1, T, and N thermocouples at a temperature of -100
°
C or less is ±2
°
C ±1 digit maximum. The
indication accuracy of the U, L1 and L2 thermocouples at any temperature is ±2
°
C ±1 digit maximum.
The indication accuracy of the B thermocouple at a temperature of 400
°
C or less is unrestricted.
The indication accuracy of the R and S thermocouples at a temperature of 200
°
C or less is ±3
°
C ±1 digit maximum.
The indication accuracy of the W thermocouple is ±1 digit max. of whichever is the greater of ±0.3% or ±3
°
C of the indicated
value.
The indication accuracy of the PLII thermocouple is ±1 digit max. of whichever is the greater of ±0.3% or ±2
°
C of the indicated
value.
*2On a position-proportional control type, 1 to 3999.
F
Heter Burnout Alarm
Max. heater current
Single-phase 50 A VAC (see note 1)
Heater current value display accuracy
5%FS
1 digit max.
Heater burnout alarm setting range
0.1 to 49.9 A (in units of 0.1 A) see note 2)
Min. detection ON time
190 ms (see note 3)
Note:
1. Use the K2CU-F
VV
A-
V
GS (with gate input terminals) for the detection of three-phase heater burnout.
2. The heater burnout alarm is always OFF if the alarm is set to 0.0A and always ON if the alarm is set to 50.0A.
3. No heater burnout detection or heater current value measurement is possible if the control output (heat) is ON for less
than 190ms.
(*2)