CHAPTER 5 PARAMETERS
E5AK
5--6
·
The parameters in this mode can be used only when the “security” parameter (pro-
tect mode) is set to “0” to “4”.
·
The “PV/SP” parameter can be used when the “security” parameter is set to “5” or
“6”. However, note that the SP cannot be changed when it is set to “6”.
·
This mode is used for monitoring the process value, set point and manipulated vari-
able during operation, and for checking and setting the SP setting value. It is also
used for starting and stopping controller operation.
·
To select this mode when in the levels 1 and 2, setup, expansion, option and calibra-
tion modes, press the
key for 1 second minimum. The display changes to the
menu display. If you select [
] then press
key for 1 second minimum, the
controller enters the level 0 mode.
·
To select parameters in this mode, press the
key. To change parameter settings,
use the
or
keys.
·
The following table shows the parameters supported in this mode and the page where
the parameter is described.
Symbol
Parameter Name
Page
PV/SP
5-6
Remote SP monitor
5-7
Set point during SP ramp
5-8
MV monitor (heat)
5-8
MV monitor (cool)
5-8
Vavle opening monitor
5-9
Run/Stop
5-9
PV/SP
·
The process value is displayed on the No.1 display, and the set point is displayed on
the No.2 display. The set point can be set.
·
Either of the local SP or remote SP is displayed as the set point depending on the SP
mode. In the remote SP mode, the set point is only monitored.
Process value
Set point
[RSP] LED not lit
Monitor only
[RSP] LED lit
Local SP mode
Remote SP mode
·
The selected set point is linked when the multi-SP function is in use in the local SP
mode. For example, when set point 1 is selected, set point 1 is displayed on the No.2
display, and the setting of the “set point 1” parameter (level 1 mode) also is changed
when the value of set point 1 is changed.
·
The decimal point position is dependent on the selected sensor during temperature
input and on the results of scaling during analog input.
Level 0 Mode
Function