CHAPTER 5 PARAMETERS
E5AK
5--42
HBA latch
Conditions of Use
The HBA output function must be
assigned.
·
When this parameter is set to ON, the heater burnout alarm is held until either of the
following conditions is satisfied:
a Set the heater burnout set value to “0.0”.
b Reset the controller. (Turn the controller’s power OFF then back ON again.)
Setting Range
Default
[
]: Enabled/[
]: Disabled
[
]
F
Related article
4.5 How to Use the Heater Burnout Alarm (page 4-13)
F
Related parameters
“Control output assignment 1” “Control output assignment 2” “Auxiliary output
assignments 1” “Auxiliary output assignments 2” (setup mode)
E5AK-AA2 AC100-240
E5AK-AA2 AC/DC24
Motor Calibration
Conditions of Use
The control must be position-proportion
control.
·
Executes motor calibration. Be sure to execute this parameter when monitoring the
valve opening. (Displays cannot be switched while motor calibration is being
executed.)
·
The “travel time” parameter is also reset when this parameter is executed.
·
The default setting is “
”.
·
Motor calibration is executed when “
” is selected.
·
After motor calibration is completed, the setting automatically returns to “
”.
F
Related article
4.1 Selecting the Control Method/Position-proportional Control (page 4-3)
F
Related parameter
“Travel time” (option mode)
E5AK-PRR2 AC100-240
E5AK-PRR2 AC/DC24
Option Mode