208
Troubleshooting Tables
Section 9-3
Memory
error
Lit
OFF
Lit
OFF
MEM-
ORY ERR
0360 Hex
00 Hex
F1 Hex
F1 Hex
SR
24904
Library checksum error has
occurred (-V1 unit only).
Create a ladder library, or download
backup data in memory card.
SR
24906
The object program area overflowed
when the user program was com-
piled.
Reduce the size of the program or
try Normal Execution Mode if High-
speed Execution Mode was used
initially.
SR
24907
Illegal instructions were found in a
program, or a ladder library (-V1
unit only).
Remove illegal instructions from the
program or the ladder library. After
that, transfer the program again.
SR
24908
Out-of-range operands were found
in the program.
Make sure that all addresses used
in the program are supported by the
Unit and retransfer the program.
SR
24909
A flash memory error has occurred
in the unit.
A sum error has occurred at reading
data from memory card (only cus-
tomizable unit -V1).
Switch to PROGRAM mode and
turn OFF the power once, then ON
again. Then transfer the program
again. For HCA22(-V1) and
HCA12(-V1), check bits 12 to 15 of
AR 17 and bits 08 to 15 of AR 03
and perform the following:
If there is an error in the user adjust-
ments, clear the error and readjust
the settings. If there is an error in
default adjustments, replace the
unit. Finally, read data from memory
card.
SR
24910
A checksum error occurred in read-
only words in DM Area.
Reset the read-only words in DM
Area.
SR
24911
A checksum error occurred in Unit
Setup Area.
Reset the Unit Setup Area.
SR
24912
A checksum error occurred in the
user program or an instruction has
been used incorrectly.
Retransfer the program.
SR
24913
A checksum error has occurred in
an expansion instruction’s data.
Set all of the expansion instruction
settings again and retransfer the
program.
Lit
---
---
OFF
---
---
---
SR
24914
Memory contents could not be held
for a power interruption.
Download or reinput the required
data.
Error
Unit indicators
Error
message
Error log
(SIOU code,
details 1,
details 2)
SR 23500
to
SR 23507
Error
flags
Meaning and corrective
measures
RUN OPN
ERC
ERH
Summary of Contents for CS1W-HCA12-V1
Page 2: ......
Page 6: ...vi...
Page 20: ...xx Conformance to EC Directives 7...
Page 38: ...18 Models and System Configurations Section 1 2...
Page 78: ...58 Fail safe Circuits Section 3 5...
Page 138: ...118 AR Area Section 6 4...
Page 204: ...184 Improved Instructions Section 7 14...
Page 222: ...202 Cycle Time Section 8 3...
Page 240: ...220 Troubleshooting Flowcharts Section 9 5...
Page 244: ...224 Precautions when Using the CX Programmer Appendix A...
Page 252: ......
Page 253: ......