157
Analog Input Functions
Section 7-9
AR 18
00
Adjustment mode
command (valid
when DM6631 =
5A5A Hex)
Analog
Input/Ana-
log Output 1
Adjust-
ment
enable
ON: Adjustment invalid
OFF: Adjustment valid
At the rise of this bit, an initial
value (offset or gain) corre-
sponding to I/O signal ranges
is transferred to AR 19/20
(adjustment value monitor
bits).
User
Enabled
01
Analog Out-
put 2
02
Analog
Input/Ana-
log Output
1/2
Adjust-
ment
mode
specifi-
cation
OFF: Offset adjustment
ON: Gain adjustment
03
Analog
Input/Ana-
log Output 1
Adjust
object
specifi-
cation
OFF: Analog output
ON: Analog input
06
Analog
Input/Ana-
log Output
1/2
Adjust-
ment
value
clear (to
default
data)
OFF to ON: the data is put
back to the factory default set-
ting.
07
Analog
Input/Ana-
log output 1/
2
Adjust-
ment
value
set (reg-
istra-
tion)
OFF to ON: the value in 16-bit
resolution of AR 19/20
(adjustment value monitor
bits) is stored in Flash mem-
ory. The value is used in the
next operation.
08
Analog
Input/Ana-
log output 1/
2
Adjust-
ing
opera-
tion
error
This is turned ON by faulty
operations. (Ex: Turning ON
both adjustment enable flags
for analog input and output at
the same time, etc)
Unit
15
Analog
Input/Ana-
log Output
1/2
Start-
ing
adjust-
ment
mode
Stays ON in adjustment
mode. (when DM6631 = 5A5A
Hex)
Address
Bits
Function
Details
Controlled
by
Forced
set/reset
Summary of Contents for CS1W-HCA12-V1
Page 2: ......
Page 6: ...vi...
Page 20: ...xx Conformance to EC Directives 7...
Page 38: ...18 Models and System Configurations Section 1 2...
Page 78: ...58 Fail safe Circuits Section 3 5...
Page 138: ...118 AR Area Section 6 4...
Page 204: ...184 Improved Instructions Section 7 14...
Page 222: ...202 Cycle Time Section 8 3...
Page 240: ...220 Troubleshooting Flowcharts Section 9 5...
Page 244: ...224 Precautions when Using the CX Programmer Appendix A...
Page 252: ......
Page 253: ......